Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Carlo Gavazzi SHSUCOTD is a wall-mounted Smart Dupline CO2 and temperature sensor with LCD display, NDIR sensing, a 0–2000 ppm CO2 range and -20 to +50 °C temperature measurement for intelligent building automation.
£346.77
The Carlo Gavazzi SHSUCOTD is a Smart Dupline CO2 and temperature sensor with integrated LCD display, designed for indoor air-quality monitoring and intelligent building automation. The wall-mounted sensor continuously measures carbon dioxide concentration and ambient temperature, providing valuable environmental data to a compatible Smart Dupline control system.
The SHSUCOTD uses Non-Dispersive Infrared (NDIR) technology with an E+E dual-source infrared sensing system to measure CO2 concentrations from 0 to 2000 ppm. CO2 accuracy is specified at better than ±(50 ppm + 2% of the measured value) under reference conditions, while the integrated temperature sensor measures from -20 to +50 °C with an accuracy of ±0.5 °C.
An integrated LCD display with LED backlight allows measured values to be viewed directly at the installation point. The front touch button activates the backlight and allows the displayed signal type to be changed. The SHSUCOTD is powered directly from the Dupline bus, requiring only the bus connection for power and communication and helping simplify installation in Smart Dupline building automation systems.
Carbon dioxide concentration is an important indicator of indoor air quality in occupied spaces. As people occupy a room, CO2 levels can rise if ventilation is insufficient. By continuously measuring concentrations from 0 to 2000 ppm, the SHSUCOTD can provide Smart Dupline systems with information that can be used as part of demand-controlled ventilation and building-management strategies.
The integrated temperature sensor adds room-temperature information to the same device, allowing both environmental parameters to be incorporated into building automation logic. Local values can also be viewed directly on the LCD display, while the front touch button activates the backlight and allows the user to change which measured signal is displayed.
| Manufacturer | Carlo Gavazzi |
|---|---|
| Series | Smart Dupline |
| Model | SHSUCOTD |
| Product type | CO2 and temperature sensor with display |
| Fieldbus type | Wired |
| Sensing functions | CO2 and temperature |
| CO2 measurement principle | Non-Dispersive Infrared Technology (NDIR) |
| CO2 sensing element | E+E Dual Source Infrared System |
| CO2 measurement range | 0–2000 ppm |
| CO2 accuracy | <±(50 ppm + 2% of measured value) at 25 °C and 1013 mbar |
| CO2 response time | Typically 300 s |
| CO2 temperature dependence | Typically 2 ppm CO2/°C from 0 to 50 °C |
| CO2 long-term stability | Typically 20 ppm/year |
| Temperature measurement range | -20 to +50 °C |
| Temperature accuracy | ±0.5 °C |
| Temperature sample rate | 5 s |
| Display | LCD with LED backlight |
| User interface | Front touch button |
| Power supply | Supplied by Dupline bus |
| Dupline nominal voltage | 8.2 V |
| Minimum Dupline voltage | 5.5 V |
| Maximum Dupline voltage | 10 V |
| Maximum Dupline current | 10 mA |
| Power-on delay | ≤3 s |
| Mounting | Surface / wall mounting |
| Dimensions | 80 × 90 × 26 mm |
| E-Number (Sweden) | 1701635 |
| E-Number (Norway) | 4540642 |
The SHSUCOTD measures both carbon dioxide concentration and ambient temperature. CO2 measurement covers 0–2000 ppm, while temperature measurement covers -20 to +50 °C.
The SHSUCOTD uses Non-Dispersive Infrared (NDIR) technology with an E+E dual-source infrared sensing system for CO2 measurement.
Yes. The SHSUCOTD features an LCD display with LED backlight. A touch button on the front activates the backlight and allows the displayed measurement type to be changed.
The SHSUCOTD measures carbon dioxide concentrations from 0 to 2000 ppm, with specified accuracy better than ±(50 ppm + 2% of the measured value) at 25 °C and 1013 mbar.
No. The SHSUCOTD is powered directly from the Smart Dupline bus. The same wired bus provides the connection required for the sensor's Smart Dupline communication and power.
Carlo Gavazzi SHSUCOTD combines accurate NDIR CO2 measurement, room-temperature sensing and a convenient local display in one compact Smart Dupline device, providing practical environmental data for intelligent ventilation, HVAC and building automation systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.