Finder 18.4K.9.030.0001 KNX corridor motion and presence detector with 30 m x 4 m PIR coverage, 120 m² detection area, 30 V DC KNX bus supply, five configurable datapoint outputs, dynamic lighting regulation and ETS configuration.

SKU: 18.4K.9.030.0001Alt SKU: 184K90300001MPN: 18.4K.9.030.0001
Price
List Price £186.31 ex VAT
Your Price (ex VAT) Save 25%
£139.73 25% OFF
You save £46.58 per unit
Manufacturer Lead Time Standard Manufacturer Lead Time 6-8 Weeks, Call For Express Delivery Options
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £139.73
Trade pricing is personalised to your account

Manufacturer Lead Time

£139.73

Why Choose the Finder 18.4K.9.030.0001 KNX Motion and Presence Detector?

The Finder 18.4K.9.030.0001 is a professional KNX motion and presence detector specifically designed for corridors, passageways and other long, narrow indoor spaces. Part of the Finder 18 Series, this intelligent ceiling-mounted PIR sensor combines wide-area movement detection, ambient light measurement and programmable KNX building automation functions.

Featuring a detection area of up to 30 m in length and 4 m in width, the Finder 18.4K.9.030.0001 can monitor an area of approximately 120 m² when installed under suitable conditions. Its corridor-optimised detection pattern incorporates two sensing areas, left and right, making it particularly effective for monitoring movement along extended passageways.

The detector operates directly from the KNX bus supply, with a nominal operating voltage of 30 V DC, and provides five configurable KNX output datapoints for lighting, HVAC and other building automation functions. Additional features include dynamic lighting regulation, adjustable PIR sensitivity, programmable ambient light thresholds, logic functions and master/slave operation.

Suitable for surface-mounted, recessed and suspended ceiling installations, the Finder 18.4K.9.030.0001 is a versatile solution for commercial buildings, hotels, hospitals, offices, educational facilities and intelligent building management systems.

Key Advantages

  • KNX-compatible motion and presence detector for intelligent building automation.
  • Extended corridor detection range of up to 30 m.
  • 4 m detection width for long, narrow passageways.
  • Up to 120 m² coverage under specified installation conditions.
  • Two detection areas for monitoring movement to the left and right of the sensor.
  • Five configurable KNX output datapoints for building control functions.
  • Dynamic lighting regulation helps maintain suitable illumination levels.
  • Adjustable ambient light threshold supports daylight-dependent control.
  • Adjustable PIR sensitivity allows the detection response to be tailored to the installation.
  • Master/slave functionality supports extended detection coverage.
  • Integrated logic functions for more sophisticated automation sequences.
  • Supports lighting and HVAC control through compatible KNX actuators.
  • KNX bus-powered operation avoids the need for a separate mains supply to the detector.
  • ETS 4 and later configuration compatibility.
  • Multiple ceiling mounting options for new installations and refurbishment projects.
  • IP40 protection rating for suitable indoor environments.

Key Features

  • Finder 18 Series KNX detector.
  • Type: 18.4K.
  • Model: 18.4K.9.030.0001.
  • Passive infrared movement and presence sensing.
  • Optimised detection pattern for corridors and passageways.
  • Maximum detection length: 30 m.
  • Maximum detection width: 4 m.
  • Maximum nominal detection area: 120 m².
  • Separate left and right detection areas.
  • KNX bus nominal voltage: 30 V DC.
  • KNX bus operating voltage: 21–32 V DC SELV.
  • Nominal bus current: 10 mA.
  • Five configurable KNX control outputs.
  • Additional master/slave communication functionality.
  • Dynamic lighting regulation.
  • Adjustable brightness threshold: 1–1500 lx.
  • Adjustable switch-off delay: 0.1 seconds to 18 hours.
  • Configurable PIR detection sensitivity.
  • Ambient light measurement and status reporting.
  • Movement status communication via KNX.
  • Configurable logic functions.
  • KNX programming button.
  • Compatible with ETS 4 or later.
  • Surface, recessed and suspended ceiling mounting.
  • IP40 protection rating.
  • Operating temperature: -5 to +45 °C.

Extended 30 m Corridor Detection with Dual Sensing Areas

The Finder 18.4K.9.030.0001 is designed specifically for environments where movement must be detected over a long, relatively narrow area.

Conventional ceiling-mounted presence detectors often provide circular or square detection patterns, making them suitable for offices, meeting rooms and open spaces. In corridors, however, these detection patterns may require several devices to cover the full length of the passageway.

The Finder 18.4K uses a specialised detection arrangement offering a nominal coverage area of 30 m × 4 m at a reference mounting height of 3 m.

This provides an approximate maximum detection area of 120 m², making the detector particularly suitable for long corridors in hotels, offices, hospitals and other commercial buildings.

The sensing arrangement includes two detection areas, left and right, allowing the device to monitor movement along the passageway in both directions.

Actual detection performance depends on mounting height, movement direction, environmental conditions and the characteristics of the monitored space. The manufacturer's detection diagrams should be consulted when determining the number and position of sensors required.

KNX Integration for Intelligent Building Control

The Finder 18.4K.9.030.0001 communicates through a KNX building automation bus, allowing movement and ambient light information to be used by compatible control devices throughout the installation.

KNX is a widely adopted building automation standard used to integrate lighting, heating, ventilation, air conditioning, shading and other building functions.

The detector is powered directly from the KNX bus, operating from a nominal 30 V DC supply. Finder specifies a permitted supply range of 21–32 V DC SELV and a nominal bus current of 10 mA.

Because the detector communicates using KNX telegrams, it does not require an integrated mains switching relay to control connected equipment.

Instead, the sensor sends commands or status information to compatible KNX switching actuators, dimming actuators and HVAC control devices.

This distributed control architecture allows a single sensor to participate in multiple automation functions while keeping load switching within the appropriate KNX actuators.

Five Configurable KNX Outputs for Lighting and HVAC

The Finder 18.4K.9.030.0001 provides five configurable KNX output datapoints for controlling suitable building automation functions.

These outputs can be configured to transmit commands associated with movement detection, lighting requirements and other programmed operating conditions.

For example, a corridor lighting system can be configured so that movement triggers an appropriate KNX actuator to switch on or adjust the lighting.

In another application, the detector's occupancy information can contribute to the control strategy of a compatible heating, ventilation or air conditioning system.

The device also supports logic functions, enabling more advanced relationships between sensor inputs, light levels and output commands.

These functions allow the sensor to participate in coordinated building automation rather than operating as a simple standalone motion switch.

The five outputs are KNX communication datapoints, not five physical relay contacts. Electrical loads must be connected to appropriately rated external KNX actuators.

Dynamic Lighting Regulation and Daylight-Dependent Control

One of the key features of the Finder 18.4K.9.030.0001 is its ability to support dynamic lighting regulation.

The integrated ambient light sensor monitors illumination levels within the detection area. This information can be used to adjust compatible KNX lighting systems according to the available daylight and the configured lighting requirements.

The detector provides an adjustable ambient light threshold from 1 to 1500 lx, allowing installers to select a suitable operating point for the application.

For example, corridor lighting may be configured to activate when movement is detected and the measured ambient illumination falls below the selected threshold.

Where compatible dimming actuators are installed, the KNX system can use the sensor's brightness information to regulate lighting output more dynamically.

The detector also supports a selectable function for disabling ambient light threshold control. This allows lighting commands to be generated independently of the measured brightness where the application requires it.

These capabilities can help reduce unnecessary lighting operation and improve energy efficiency in buildings with varying levels of natural light.

Adjustable PIR Sensitivity and Switch-Off Delay

The Finder 18.4K.9.030.0001 includes configurable parameters that allow its behaviour to be tailored to the characteristics of the monitored area.

The PIR sensitivity can be adjusted to suit the installation environment and expected movement patterns.

This can be useful in corridors where the sensor must detect people walking through the monitored area while reducing unwanted operation caused by conditions outside the intended detection zone.

The detector also supports an adjustable switch-off delay from 0.1 seconds to 18 hours.

Short delays may be appropriate for certain automation signals, while longer delays can be selected for lighting applications where illumination should remain available for a defined period after movement has ceased.

The appropriate delay depends on the type of space, expected occupancy and operational requirements.

All detection and timing parameters should be configured using the applicable KNX ETS application programme.

Master/Slave Operation for Extended Detection Coverage

In longer corridors or complex passageway layouts, a single detector may not provide sufficient coverage for the complete area.

The Finder 18.4K.9.030.0001 supports master/slave operation, allowing multiple compatible detectors to contribute to a coordinated KNX control arrangement.

In this configuration, additional sensors can report movement information to the designated control logic, extending the effective monitored area.

This is particularly useful in large hotels, hospitals and commercial buildings where corridors may include corners, intersections or sections longer than the nominal 30 m detection range.

Master/slave operation also supports consistent lighting behaviour across multiple detector positions.

The exact KNX group address configuration, communication objects and operating parameters must be established using the appropriate ETS application.

Configuration Using KNX ETS Software

The Finder 18.4K.9.030.0001 is designed for configuration using KNX Engineering Tool Software (ETS).

Finder specifies compatibility with ETS 4 or later versions, allowing installers to integrate the detector into a KNX project and configure its operating parameters.

During commissioning, the installer can assign the KNX individual address, configure communication objects and establish the required group address relationships.

Available configuration options include the ambient light threshold, PIR sensitivity, switch-off timing, output functions and master/slave operation.

The detector includes a KNX programming button to support device addressing and commissioning.

Correct configuration is important because the detector's behaviour depends on both its internal settings and the KNX actuators and control devices connected to the system.

The latest compatible Finder ETS application files and product documentation should be used when commissioning a new installation.

Flexible Ceiling Mounting and Installation Requirements

The Finder 18.4K.9.030.0001 supports several installation arrangements, including surface mounting, recessed ceiling mounting and suspended ceiling installation.

This flexibility makes it suitable for new commercial buildings as well as refurbishment projects where ceiling construction may vary.

For corridor applications, the sensor should be positioned according to Finder's detection diagrams to provide suitable coverage along the intended passageway.

The reference detection pattern is specified at a mounting height of 3 m. Alternative mounting heights may change the effective detection geometry and sensitivity.

The detector connects directly to the KNX bus and must be supplied from a suitable KNX power supply operating within the specified voltage range.

Its IP40 protection rating makes it suitable for appropriate indoor environments, but it is not designed for direct exposure to water or outdoor weather conditions.

The specified operating temperature range is -5 to +45 °C.

Installation and commissioning should be performed by competent personnel familiar with KNX systems and the applicable electrical installation requirements.

Important: The Finder 18.4K.9.030.0001 is intended for building automation functions. It must not be used as a substitute for a certified intruder alarm or life-safety detection system.

Typical Applications

  • KNX-controlled corridor lighting systems.
  • Hotel corridors and common areas.
  • Hospital corridors and healthcare facilities.
  • Office passageways and circulation spaces.
  • School and university corridors.
  • Commercial building lighting automation.
  • Daylight-dependent lighting regulation.
  • Energy-saving occupancy-based lighting control.
  • KNX HVAC occupancy management.
  • Building management system integration.
  • Long passageways and connecting corridors.
  • Multi-sensor master/slave detection systems.
  • Commercial property refurbishment projects.
  • Intelligent building automation installations.

Technical Specifications

Manufacturer Finder
Product series Finder 18 Series
Type 18.4K
Manufacturer part number 18.4K.9.030.0001
Product type KNX motion and presence detector
Sensor technology Passive infrared (PIR)
Primary application Corridor and passageway movement detection
Communication interface KNX
Nominal supply voltage 30 V DC via KNX bus
Permitted bus supply range 21–32 V DC SELV
Nominal bus current 10 mA
Detection area Up to 120 m²
Maximum detection length 30 m
Maximum detection width 4 m
Reference mounting height for detection pattern 3 m
Detection zones Left and right
Configurable KNX outputs 5 datapoints
Master/slave communication Supported
Dynamic lighting regulation Supported
Ambient light threshold adjustment 1–1500 lx
Switch-off delay adjustment 0.1 seconds to 18 hours
PIR sensitivity adjustment Supported
Ambient light threshold override Supported
Logic functions Supported
Light level reporting Supported via KNX
Movement status reporting Supported via KNX
Configuration software KNX ETS
ETS compatibility ETS 4 or later
Mounting methods Surface-mounted, recessed ceiling or suspended ceiling
Installation location Indoor ceiling
Electrical connection KNX bus terminal
Integrated load-switching relay No; switching is performed by compatible KNX actuators
Degree of protection IP40
Operating temperature -5 to +45 °C
Relevant standards EN 60669-1, EN 60669-2-1 and EN 50491
Product designation Finder 18.4K KNX Corridor Motion Detector PRO

Frequently Asked Questions

What is the Finder 18.4K.9.030.0001 used for?

The Finder 18.4K.9.030.0001 is a KNX motion and presence detector designed for corridors and long, narrow indoor spaces. It uses PIR sensing and ambient light measurement to support automated lighting, HVAC and other compatible KNX building control functions.

What is the detection range of the Finder 18.4K.9.030.0001?

The Finder 18.4K.9.030.0001 provides a nominal detection area of up to 30 m long and 4 m wide, equivalent to approximately 120 m² at a reference mounting height of 3 m. Actual coverage depends on installation height, movement direction and environmental conditions.

What supply voltage does the Finder 18.4K.9.030.0001 require?

The Finder 18.4K.9.030.0001 is powered directly from the KNX bus, with a nominal supply voltage of 30 V DC and a permitted operating range of 21–32 V DC SELV. Its nominal bus current is 10 mA. A separate 230 V AC supply is not required at the detector.

How many KNX outputs does the Finder 18.4K.9.030.0001 provide?

The Finder 18.4K.9.030.0001 provides five configurable KNX output datapoints for functions such as lighting and HVAC control. These are KNX communication outputs rather than physical relay contacts, so connected electrical loads must be switched or regulated using compatible KNX actuators.

Can the Finder 18.4K.9.030.0001 be configured using ETS software?

Yes. The Finder 18.4K.9.030.0001 is compatible with KNX ETS 4 or later. Installers can configure the ambient light threshold, PIR sensitivity, switch-off delay, KNX communication objects, output functions and master/slave operation through the appropriate ETS application programme.

Designed for KNX Integrators, Electrical Engineers and Building Automation Professionals

The Finder 18.4K.9.030.0001 KNX motion and presence detector provides extended 30 m × 4 m corridor coverage, five configurable KNX outputs and advanced dynamic lighting regulation in a versatile ceiling-mounted design. With adjustable PIR sensitivity, ambient light measurement, ETS configuration and master/slave capability, it offers an intelligent solution for energy-efficient lighting and building automation in commercial and public buildings.