Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB EPX-PB812 is an 800 A 12-way Protecta Power MCCB distribution panelboard measuring 1700 × 1000 × 300 mm, designed for reliable high-capacity low-voltage power distribution in commercial and industrial installations.
£6,092.35
The ABB EPX-PB812 is a high-capacity 800 A 12-way moulded case circuit breaker (MCCB) distribution panelboard designed for reliable low-voltage electrical power distribution in commercial, industrial and infrastructure installations. As part of the ABB Protecta Power enclosure range, this panelboard provides a modular solution for distributing electrical power through multiple protected outgoing circuits while supporting straightforward installation, maintenance and future system modifications.
The EPX-PB812 incorporates an 800 A rated busbar system and provides 12 outgoing ways for compatible ABB Tmax XT moulded case circuit breakers. The Protecta Power system features innovative plug-in circuit breaker connections, an improved finger-safe busbar stack and modular enclosure accessories designed to simplify electrical distribution assembly and improve accessibility for authorised installation and maintenance personnel.
Measuring 1700 mm high × 1000 mm wide × 300 mm deep, the EPX-PB812 provides a substantial yet organised enclosure arrangement for demanding electrical distribution applications. The Protecta Power system supports 415 V AC operation, a 50 kA short-time withstand current for 1 second and IP43 enclosure protection when correctly assembled with the specified components, making it suitable for appropriately designed indoor low-voltage distribution installations.
High-capacity moulded case circuit breaker panelboards are essential components in commercial and industrial low-voltage electrical distribution systems. They provide a centralised arrangement for distributing electrical power to multiple outgoing circuits while accommodating suitable protective devices for overload, short-circuit and isolation requirements.
The ABB EPX-PB812 combines an 800 A rated busbar system with a 12-way outgoing configuration, providing a practical solution for electrical installations requiring substantial distribution capacity. Its rated short-time withstand current of 50 kA for 1 second supports appropriately engineered distribution assemblies where prospective fault levels and protective device coordination have been assessed.
ABB Protecta Power incorporates an innovative plug-in MCCB connection system using spring-loaded contacts. This arrangement reduces the number of conventional bolted circuit breaker connections and is designed to maintain reliable electrical contact during normal operation. The improved finger-safe busbar stack provides additional protection against accidental direct contact with internal busbar components.
The modular enclosure design also supports electrical system flexibility. Compatible ABB Tmax XT circuit breakers can be selected to provide the required circuit protection characteristics, while optional metering and monitoring accessories allow electrical engineers to incorporate power measurement and energy management functions into the completed distribution assembly.
With its 1700 × 1000 × 300 mm enclosure format, durable steel construction and coordinated cable entry arrangements, the EPX-PB812 is designed to support professional electrical panel building and long-term distribution system maintenance. The completed installation must be assembled in accordance with ABB instructions, with appropriate incoming and outgoing protective devices, connection kits, cable terminations and accessories selected for the required electrical performance.
Tick the specs you need, then view products that match.
| Metering | No metering | |
|---|---|---|
| Device Type | Panel Board | |
| Number of Outgoing Ways | 12 | |
| Current | 800 A | |
| Incomer | MCCB | |
| Product Series | ABB Protecta Power | |
| Series | Protecta Power Enclosures | |
| ABB order code | 1SKV413179S0001 | |
| Product type | MCCB distribution panelboard | |
| Product category | Low-voltage electrical distribution enclosures | |
| Rated busbar current | 800 A | |
| Number of outgoing ways | 12 | |
| Rated operational voltage (Ue) | 415 V AC | |
| Rated frequency | 50 Hz | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Rated short-time withstand current (Icw) | 50 kA for 1 s | |
| Height | 1700 mm | |
| Width | 1000 mm | |
| Depth | 300 mm | |
| Dimensions (H × W × D) | 1700 × 1000 × 300 mm | |
| Useful outgoing breaker mounting length | 720 mm | |
| Enclosure protection rating | IP43 with door in the specified assembled configuration | |
| Mechanical impact resistance | IK07 | |
| Busbar touch protection | IP20 finger-safe design | |
| Enclosure material | Cold-rolled sheet steel | |
| Enclosure sheet thickness | 1.5 mm | |
| Colour | RAL 7035 | |
| Surface finish | Textured powder coating | |
| Door opening angle | 180° | |
| Door locking arrangement | Three-point locking | |
| Cable entry | Removable top, bottom and side gland plate arrangements | |
| Busbar connection technology | Spring-loaded plug-in circuit breaker connectors | |
| Compatible circuit breaker family | Selected ABB Tmax XT MCCBs | |
| Neutral and earth arrangements | Separate copper neutral and protective earth bars | |
| Applicable assembly standards | BS EN IEC 61439-1 and BS EN IEC 61439-2 | |
| Related 800 A panelboards | EPX-PB808 (8-way) and EPX-PB818 (18-way) | |
| Related 400 A panelboard | EPX-PB412 (12-way) | |
| Application | Commercial, industrial and infrastructure electrical distribution |
The ABB EPX-PB812 is an 800 A 12-way MCCB distribution panelboard designed to distribute electrical power to multiple protected outgoing circuits in commercial, industrial and infrastructure low-voltage installations.
The EPX-PB812 features an 800 A rated busbar system. The operating current of the completed installation depends on the selected incoming protective device, outgoing circuit requirements and overall electrical system design.
The panelboard provides 12 outgoing ways for compatible ABB moulded case circuit breakers. The Protecta Power 12-way configuration provides a useful outgoing breaker mounting length of 720 mm.
The EPX-PB812 measures 1700 mm high × 1000 mm wide × 300 mm deep, providing a coordinated enclosure format for the ABB Protecta Power 800 A 12-way distribution system.
The ABB Protecta Power system has a specified rated short-time withstand current of 50 kA for 1 second. The complete electrical installation must be assessed for prospective fault current, protective device coordination and the applicable assembly requirements.
The specified Protecta Power assembly provides IP43 enclosure protection with the appropriate door fitted and IK07 mechanical impact resistance. Its improved finger-safe busbar stack provides IP20 protection against direct contact. These ratings depend on correct assembly and installation.
The EPX-PB812 belongs to the ABB Protecta Power system, which supports selected ABB Tmax XT moulded case circuit breakers, including compatible XT5 and XT6 arrangements. The correct incoming and outgoing circuit breakers and connection kits must be selected according to the required electrical ratings and ABB assembly instructions.
Yes. The ABB Protecta Power system supports optional electrical energy metering and power monitoring arrangements. Compatible meters, current transformers, communication accessories and enclosure components must be specified separately to suit the required monitoring functions.
Both panelboards provide 12 outgoing ways and share the nominal enclosure dimensions of 1700 × 1000 × 300 mm. The EPX-PB812 has an 800 A rated busbar system, while the EPX-PB412 has a 400 A rated busbar system.
ABB Protecta Power MCCB panelboards are engineered to provide reliable, flexible and accessible low-voltage power distribution. The EPX-PB812 combines an 800 A rated busbar system, 12 outgoing ways, finger-safe busbar technology and modular ABB Tmax XT circuit breaker integration, making it a practical choice for electrical contractors, consultants and panel builders working on demanding commercial and industrial distribution projects.
We use cookies