Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB EPH-S11102 (1TVC151800S3098) is a compact 2-way Protecta Home steel consumer unit with a factory-fitted 100 A RCCB incomer, shrouded busbar, neutral and earth terminal bars, and nominal dimensions of 250 × 190 × 105 mm for residential and light commercial electrical distribution.
£147.04
The ABB EPH-S11102 (1TVC151800S3098) is a compact 2-way, 100 A RCCB consumer unit from the ABB Protecta Home range, designed for residential and light commercial electrical distribution. Featuring a factory-fitted residual current circuit breaker (RCCB) as the incoming device, this consumer unit provides residual current protection for compatible outgoing circuits within a durable steel enclosure.
Unlike a conventional main switch-only consumer unit, the ABB EPH-S11102 incorporates a 100 A RCCB incomer, combining manual switching with residual current protection. This arrangement makes it a practical choice for smaller electrical distribution installations where a limited number of outgoing circuits require a common residual current protective device.
ABB's Protecta Home selection information confirms a 2-way, 2-module configuration with nominal enclosure dimensions of 250 × 190 × 105 mm (H × W × D). The unit features a RAL 7035 grey steel enclosure and is supplied with a shrouded busbar, earth and neutral terminal bars, and installation instructions, providing a convenient starting point for professional electrical installations.
The ABB EPH-S11102 belongs to the 100 A RCCB incomer section of the Protecta Home consumer unit range. Its factory-fitted RCCB monitors the balance of current flowing through the conductors it protects and disconnects the supply when residual current exceeds the device's specified operating threshold. This functionality is particularly important in electrical installations where residual current protection is required.
The 100 A rating describes the RCCB's rated current, not its residual operating current. The residual operating current, RCCB type and other protective characteristics must be confirmed from the actual fitted device before installation. A 100 A RCCB must not be assumed to provide overload or short-circuit protection: appropriate upstream protection and correctly selected outgoing overcurrent protective devices remain necessary.
With two outgoing ways, the EPH-S11102 is suited to small circuit groups and dedicated distribution requirements. The supplied shrouded busbar, neutral bar and earth bar help installers arrange compatible protective devices and conductors neatly within the enclosure. The final circuit configuration must follow ABB's compatibility and assembly instructions.
The Protecta Home steel consumer unit range is designed to BS EN 61439-3, covering low-voltage distribution boards intended to be operated by ordinary persons. Electrical installations must also comply with applicable requirements of BS 7671. The RCCB incomer provides common residual current protection, meaning an RCCB trip can disconnect all outgoing circuits supplied through it; circuit selection should therefore consider continuity of supply and the requirements of the installation.
Tick the specs you need, then view products that match.
| Material | Steel | |
|---|---|---|
| Device Type | Consumer Unit | |
| Incomer | RCCB | |
| Number of Outgoing Ways | 2 | |
| Module Capacity | 2 modules | |
| Current | 100 A | |
| Product Series | ABB Protecta Home | |
| Product group | Protecta Home | |
| ABB order code | 1TVC151800S3098 | |
| Manufacturer description | EPH-S11102 2W 100A RCCB | |
| Product type | RCCB incomer consumer unit | |
| Product category | Consumer units and electrical distribution boards | |
| Number of outgoing ways | 2 | |
| Number of modules | 2 | |
| Incoming protective device | RCCB | |
| RCCB rated current | 100 A | |
| RCCB function | Residual current protection and manual switching | |
| Enclosure material | Steel | |
| Enclosure colour | RAL 7035 grey | |
| Product family standard | BS EN 61439-3 | |
| Busbar | Shrouded busbar supplied | |
| Neutral connections | Neutral terminal bar supplied | |
| Protective earth connections | Earth terminal bar supplied | |
| Nominal height | 250 mm | |
| Nominal width | 190 mm | |
| Nominal depth | 105 mm | |
| Nominal dimensions (H × W × D) | 250 × 190 × 105 mm | |
| Outgoing circuit protection | Compatible modular protective devices, selected separately | |
| Typical application | Residential and light commercial electrical distribution | |
| Installation requirements | ABB instructions and applicable electrical installation regulations |
The ABB EPH-S11102 is a 2-way Protecta Home consumer unit with a factory-fitted 100 A RCCB incomer. It is designed to house compatible outgoing circuit protection devices in residential and light commercial electrical distribution installations.
The EPH-S11102 provides 2 outgoing ways and 2 modular positions, according to ABB's Protecta Home selection guide. The installed protective devices must be compatible with the consumer unit and its approved assembly arrangement.
The consumer unit incorporates a 100 A RCCB incomer. This is the rated current of the device and should not be confused with its residual operating current, which must be verified from the fitted RCCB specification.
The EPH-S11102 is an RCCB incomer consumer unit, rather than the separate main switch-only configuration. Its factory-fitted RCCB provides manual switching and residual current protection. A separate 100 A main switch-disconnector is not identified in the manufacturer description for this model.
No. The factory-fitted 100 A RCCB provides residual current protection but does not independently provide overload or short-circuit protection. Suitable upstream and outgoing overcurrent protective devices must be selected for the electrical installation.
ABB lists nominal enclosure dimensions of 250 mm high, 190 mm wide and 105 mm deep for the EPH-S11102.
The EPH-S11102 features a steel enclosure finished in RAL 7035 grey. It belongs to ABB's Protecta Home steel consumer unit range.
ABB specifies that Protecta Home steel consumer units are supplied with the appropriate factory-fitted incoming device, a shrouded busbar, neutral and earth terminal bars, and installation instructions. For the EPH-S11102, the incoming device is a 100 A RCCB.
The EPH-S11102 is a 2-way consumer unit with a 100 A RCCB incomer, while the EPH-S10002 is a 2-way consumer unit with a 100 A main switch-disconnector. Both have nominal dimensions of 250 × 190 × 105 mm, but their incoming device functions differ.
The ABB Protecta Home steel consumer unit range is designed to BS EN 61439-3. Installation must also comply with applicable requirements of BS 7671 and the manufacturer's instructions.
The official ABB order code is 1TVC151800S3098. The manufacturer model is EPH-S11102, described as EPH-S11102 2W 100A RCCB within the Protecta Home product group.
ABB Protecta Home consumer units combine durable steel enclosures with practical factory-fitted incoming devices and organised modular distribution arrangements. The ABB EPH-S11102 2-Way 100 A RCCB Consumer Unit offers a compact solution for electrical installations requiring common residual current protection, two outgoing circuit ways and dependable ABB distribution equipment.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.