ABB OVR PV T1-T2 12.5-1000 P QS is a pluggable Type 1+2 photovoltaic surge protection device with 12.5 kA impulse current, 40 kA maximum discharge current, 20 kA nominal discharge current and 1100 V DC maximum continuous operating voltage for 1000 V solar PV installations.
£184.59
The ABB OVR PV T1-T2 12.5-1000 P QS, order code 2CTB812120R1000, is a pluggable Type 1+2 photovoltaic surge protection device (SPD) designed to protect the DC side of solar PV installations against lightning currents and transient overvoltages. As part of the ABB OVR PV surge protection range, it combines Type 1 lightning-current protection with Type 2 surge protection for demanding photovoltaic applications.
Designed for 1000 V DC photovoltaic systems, the OVR PV T1-T2 12.5-1000 P QS provides an impulse current (Iimp) of 12.5 kA with a 10/350 µs waveform, a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA. These ratings provide coordinated protection against both high-energy lightning impulses and transient surge currents within photovoltaic installations.
With a 1100 V DC maximum continuous operating voltage (Ucpv) and a 3.8 kV voltage protection level (Up), this SPD is suited to modern 1000 V DC photovoltaic arrays. Its pluggable QuickSafe construction, integrated thermal disconnection and visual status indication support straightforward inspection and maintenance in PV combiner boxes, DC distribution panels and inverter protection applications.
Photovoltaic installations can be exposed to high-energy lightning currents and induced transient overvoltages because solar arrays are often installed in exposed locations and connected by extensive DC cabling. Type 1+2 photovoltaic SPDs combine the ability to handle 10/350 µs lightning-current impulses with Type 2 protection against 8/20 µs surge currents, helping protect sensitive DC equipment throughout the installation.
The ABB OVR PV T1-T2 12.5-1000 P QS provides a 12.5 kA Type 1 impulse-current capability alongside a 40 kA maximum Type 2 discharge current. Its high-voltage DC design and pluggable construction make it suitable for coordinated protection of photovoltaic arrays, combiner boxes, DC distribution equipment and inverter inputs where robust lightning and surge protection is required.
Tick the specs you need, then view products that match.
| Impulse Current Iimp (kA) | 12.5 kA | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Product Series | ABB OVR PV T1-T2 | |
| Series | OVR PV T1-T2 | |
| Order code / MPN | 2CTB812120R1000 | |
| Product group | Surge Protection Devices | |
| Product type | Photovoltaic Type 1+2 surge protection device | |
| SPD classification | Type 1+2 / Class I+II | |
| Application | Photovoltaic DC systems | |
| Protected conductors | L+, L− | |
| Current type | DC | |
| Nominal system voltage | 1000 V DC | |
| Maximum continuous operating voltage (Ucpv) | 1100 V DC | |
| Impulse current (Iimp, 10/350 µs) | 12.5 kA | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 40 kA | |
| Voltage protection level (Up) | 3.8 kV | |
| PV short-circuit current rating (Iscpv) | 11 kA | |
| Technology | Varistor | |
| Integrated thermal disconnector | Yes | |
| Status indication | Visual | |
| Response time | <25 ns | |
| Mounting type | DIN rail | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +85 °C | |
| Storage temperature | -40 to +85 °C | |
| Maximum operating altitude | 4000 m | |
| Maximum relative humidity | 95 % | |
| Fire resistance | UL 94 V-0 | |
| Standard | IEC 61643-31 | |
| Construction | Pluggable |
The ABB OVR PV T1-T2 12.5-1000 P QS is a Type 1+2 photovoltaic surge protection device designed to protect the DC side of 1000 V solar PV installations against lightning-current impulses and transient overvoltages.
The device has an impulse current (Iimp) rating of 12.5 kA with a 10/350 µs waveform, providing high-capacity Type 1 protection against lightning-current impulses.
The OVR PV T1-T2 12.5-1000 P QS has a 20 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax), measured using an 8/20 µs waveform.
The device is designed for 1000 V DC photovoltaic systems and has a maximum continuous operating voltage (Ucpv) of 1100 V DC.
Yes. The ABB OVR PV T1-T2 12.5-1000 P QS uses a pluggable construction, allowing its protection cartridges to be replaced during maintenance without replacing the complete surge protection assembly.
ABB OVR PV surge protection devices are designed to protect photovoltaic DC installations against lightning currents and transient overvoltages, helping safeguard PV arrays, DC distribution equipment and inverter systems in commercial, industrial and utility-scale solar applications.