Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR PV T1-T2 10-1500 P TS QS combined Type 1 and Type 2 pluggable photovoltaic surge protective device for 1500 V DC systems, with 10 kA total lightning discharge current, 30 kA maximum surge discharge current and remote status signalling.
£232.53
The ABB OVR PV T1-T2 10-1500 P TS QS is a combined Type 1 + Type 2 photovoltaic surge protective device (SPD) engineered to protect high-voltage DC solar installations against lightning-current impulses and transient overvoltages. Identified by ABB order code 2CTB812101R1500, it is designed specifically for photovoltaic networks with a maximum continuous operating voltage of 1500 V DC.
As part of the ABB OVR PV QuickSafe range, this device uses a 1+1 DC protection configuration and combines lightning-current withstand capability with Type 2 surge-voltage limitation. Its pluggable construction allows protection cartridges to be replaced without changing the complete installed base, while optical status indication provides straightforward local condition checking.
The OVR PV T1-T2 10-1500 P TS QS provides a 5 kA impulse current (Iimp) per protected path and a 10 kA total discharge current (Itotal) using a 10/350 µs waveform. It also provides a 20 kA nominal discharge current (In), a 30 kA maximum discharge current (Imax) using an 8/20 µs waveform and a 5 kV voltage protection level (Up). The integrated TS remote signalling contact enables SPD condition monitoring from a remote control or monitoring system.
Large photovoltaic arrays can be particularly exposed to lightning-related and induced transient overvoltages because of their extensive outdoor DC cabling. Combined Type 1 and Type 2 SPDs provide protection against the high-energy 10/350 µs lightning-current waveform while also limiting the voltage rise associated with 8/20 µs transient surge currents.
The ABB OVR PV T1-T2 10-1500 P TS QS combines these protection functions in a photovoltaic-specific 1500 V DC design. Its pluggable QuickSafe construction facilitates maintenance, while local optical indication and TS remote signalling provide convenient monitoring of SPD condition in commercial, industrial and large-scale solar power installations.
Tick the specs you need, then view products that match.
| Impulse Current Iimp (kA) | 5 kA | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Product Series | ABB OVR PV T1-T2 QuickSafe | |
| Series | OVR PV T1-T2 QuickSafe | |
| ABB order code | 2CTB812101R1500 | |
| Product group | Surge Protection Devices | |
| Product type | Photovoltaic surge protective device | |
| SPD classification | Type 1 + Type 2 | |
| Application | Photovoltaic DC systems | |
| Protection configuration | 1+1 DC | |
| Number of conductors without earth | 2 | |
| Maximum continuous operating voltage (Ucpv) | 1500 V DC | |
| Impulse current (Iimp, 10/350 µs) | 5 kA per protected path | |
| Total discharge current (Itotal, 10/350 µs) | 10 kA | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 30 kA | |
| Voltage protection level (Up) | 5 kV | |
| Short-circuit current rating | 11 kA | |
| Remote signalling | Yes, TS contact | |
| Status indication | Optical | |
| Cartridge type | Pluggable | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Maximum flexible conductor cross-section | 25 mm² | |
| Maximum solid conductor cross-section | 35 mm² | |
| Construction width | 3 modular spaces | |
| Mounting | DIN rail | |
| Weight | 0.497 kg | |
| Compatible replacement cartridge | OVR PV T1-T2 10-1500 C QS | |
| Replacement cartridge order code | 2CTB812102R1500 | |
| EAN | 4053546034691 |
It is a combined Type 1 and Type 2 photovoltaic surge protective device designed to protect 1500 V DC PV circuits, solar inverters and associated equipment against lightning-current impulses and transient overvoltages.
The device provides an impulse current (Iimp) of 5 kA per protected path and a total discharge current (Itotal) of 10 kA using the 10/350 µs lightning-current waveform.
The OVR PV T1-T2 10-1500 P TS QS has a nominal discharge current (In) of 20 kA and a maximum discharge current (Imax) of 30 kA using an 8/20 µs waveform.
The TS designation indicates remote signalling, allowing the condition of the surge protective device to be monitored remotely in addition to its local optical status indication.
Yes. The ABB OVR PV T1-T2 10-1500 P TS QS uses pluggable protection cartridges. The corresponding replacement cartridge is the ABB OVR PV T1-T2 10-1500 C QS, order code 2CTB812102R1500.
ABB OVR PV surge protective devices provide coordinated lightning-current and transient overvoltage protection for high-voltage photovoltaic installations, helping safeguard solar arrays, DC distribution equipment and sensitive inverter electronics.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.