ABB OVR PV T1-T2 5-1000 P QS is a pluggable Type 1+2 photovoltaic surge protection device with 5 kA impulse current, 40 kA maximum discharge current, 20 kA nominal discharge current and 1100 V DC maximum continuous operating voltage for solar PV installations.
£147.64
The ABB OVR PV T1-T2 5-1000 P QS, order code 2CTB812050R1000, is a pluggable Type 1+2 photovoltaic surge protection device (SPD) designed to protect DC photovoltaic installations against lightning currents and transient overvoltages. As part of the ABB OVR PV surge protection range, it provides coordinated protection for solar PV systems operating at nominal voltages up to 1000 V DC.
Designed specifically for photovoltaic applications, the OVR PV T1-T2 5-1000 P QS uses a 1+1 DC protection configuration and protects both L+ and L− lines. It provides an impulse current (Iimp) of 5 kA with a 10/350 µs waveform, a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA, providing effective protection against both lightning-current impulses and induced surge events.
With a 1000 V DC nominal system voltage, 1100 V DC maximum continuous operating voltage (Ucpv) and a 3.8 kV voltage protection level (Up), this SPD is engineered for modern photovoltaic arrays and DC distribution systems. Its pluggable three-module design, integrated thermal disconnector and visual status indication support straightforward installation, inspection and maintenance.
Photovoltaic installations can be exposed to transient overvoltages generated by lightning activity and switching events, particularly where long DC cables connect exposed solar arrays to inverters and other electrical equipment. Type 1+2 photovoltaic SPDs combine lightning-current handling with surge protection to help limit damaging transient voltages within the DC side of a solar installation.
The ABB OVR PV T1-T2 5-1000 P QS is designed specifically for high-voltage PV networks. Its 1100 V DC continuous operating capability, 5 kA 10/350 µs impulse-current rating and 40 kA maximum discharge current provide coordinated protection for photovoltaic arrays, combiner boxes and inverter DC inputs, while its pluggable cartridges simplify ongoing system maintenance.
Tick the specs you need, then view products that match.
| Impulse Current Iimp (kA) | 5 kA | |
|---|---|---|
| Product Series | ABB OVR PV T1-T2 | |
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Series | OVR PV T1-T2 | |
| Order code / MPN | 2CTB812050R1000 | |
| Product group | Surge Protection Devices | |
| Product type | Photovoltaic Type 1+2 surge protection device | |
| SPD classification | Type 1+2 / Class I+II | |
| Application | Photovoltaic DC systems | |
| Protection configuration | 1+1 DC | |
| Protected lines | L+, L− | |
| Current type | DC | |
| Nominal system voltage (Un) | 1000 V DC | |
| Maximum continuous operating voltage (Ucpv) | 1100 V DC | |
| Impulse current (Iimp, 10/350 µs) | 5 kA | |
| Total discharge current (Itotal, 10/350 µs) | 5 kA | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 40 kA | |
| Voltage protection level (Up) | 3.8 kV | |
| PV short-circuit current rating (Iscpv) | 11 kA | |
| PV operating current (Icpv) | 50 A | |
| Technology | Varistor | |
| Integrated thermal disconnector | Yes | |
| Status indicator | Yes | |
| Safety reserve | No | |
| Response time | ≤25 ns | |
| Mounting type | DIN rail | |
| Module width | 3 modules | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +85 °C | |
| Storage temperature | -40 to +85 °C | |
| Maximum operating altitude | 4000 m | |
| Maximum humidity | 95 % | |
| Maximum solid conductor size | 35 mm² | |
| Maximum flexible conductor size | 25 mm² | |
| Stripping length | 12.5 mm | |
| Fire resistance | UL 94 V-0 | |
| Standards | IEC 61643-31 / EN 50539-11, UL 1449 4th Edition | |
| Dimensions (H × W × D) | 95 × 54 × 86 mm | |
| Construction | Pluggable |
The ABB OVR PV T1-T2 5-1000 P QS is a Type 1+2 photovoltaic surge protection device designed to protect the DC side of solar PV installations against lightning-current impulses and transient overvoltages.
The device is designed for a nominal system voltage of 1000 V DC and has a maximum continuous operating voltage (Ucpv) of 1100 V DC.
The OVR PV T1-T2 5-1000 P QS has an impulse current (Iimp) of 5 kA with a 10/350 µs waveform, a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA.
The ABB OVR PV T1-T2 5-1000 P QS provides a voltage protection level (Up) of 3.8 kV, helping limit transient overvoltages reaching photovoltaic inverters and other downstream DC equipment.
Yes. The OVR PV T1-T2 5-1000 P QS has a pluggable construction, and its replaceable protection cartridge is the ABB OVR PV T1-T2 5-1000 C QS.
ABB OVR PV surge protection devices are designed to protect photovoltaic installations against lightning currents and transient overvoltages, helping safeguard PV arrays, DC distribution equipment and inverter systems in residential, commercial and industrial solar applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.