Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB T7N-D/PV 1000 UL 4P Fixed Front Terminals DC Switch-Disconnector – 1000 A – 1000 V DC – Stored Energy Operating Mechanism – UL/CSA – Photovoltaic (ABB order code 1SDA070448R1).
£4,576.40
The ABB 1SDA070448R1 is a T7N-D/PV 1000 MCS UL four-pole fixed switch-disconnector designed for high-power DC applications up to 1000 V DC, featuring front terminals and a stored-energy operating mechanism.
Rated at 1000 A, this ABB Tmax T switch-disconnector provides an 18 kA short-time withstand current for 1 s and an 8 kV impulse withstand voltage, supporting demanding photovoltaic and high-power DC distribution installations.
The 1SDA070448R1 uses an MCS configuration without magnetic protection, complies with UL requirements and provides a robust solution for DC isolation and switching within photovoltaic and renewable-energy electrical systems.
The ABB 1SDA070448R1 is designed for photovoltaic installations and other high-power DC applications requiring reliable switching and isolation at up to 1000 V DC. Its 1000 A current rating and four-pole configuration make it suitable for demanding DC distribution assemblies.
As part of the ABB Tmax T-D/PV range for 1000 V DC applications, the T7N-D/PV 1000 MCS UL combines a fixed construction, front terminals and stored-energy operating mechanism for integration into industrial and renewable-energy electrical equipment.
Tick the specs you need, then view products that match.
| Voltage | 1000 V DC | |
|---|---|---|
| Device Type | MCCB switch-disconnector | |
| Supply Type | DC | |
| Poles | 4-pole | |
| Brand | ABB | |
| Product ID | 1SDA070448R1 | |
| Series | Tmax T | |
| Product Type | Switch-disconnector | |
| Sub-Type | T7N-D/PV 1000 | |
| Rated Current | 1000 A | |
| Rated Uninterrupted Current (Iu) | 1000 A | |
| Rated Voltage (Ur) | 1000 V DC | |
| Rated Operational Voltage | 1000 V DC | |
| Rated Insulation Voltage (Ui) | 1000 V DC | |
| Rated Short-Time Withstand Current (Icw) | 18 kA for 1 s | |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | |
| Number of Poles | 4 | |
| Construction | Fixed | |
| Terminal Configuration | Front terminals | |
| Operating Mechanism | Stored energy | |
| Magnetic Protection | None; MCS configuration | |
| Dimensions (H × W × D) | 268 × 280 × 178 mm | |
| Product Weight | 17.5 kg | |
| Standards | UL | |
| Environmental Compliance | RoHS | |
| EAN | 8015644714949 | |
| Manufacturer | ABB | |
| Model | T7N-D/PV 1000 UL | |
| Manufacturer part number | 1SDA070448R1 |
The ABB 1SDA070448R1 is a T7N-D/PV 1000 MCS UL four-pole fixed switch-disconnector with front terminals and a stored-energy operating mechanism for 1000 V DC applications.
The ABB 1SDA070448R1 has a rated uninterrupted current of 1000 A.
The device has a rated operational voltage and rated insulation voltage of 1000 V DC, with an 8 kV rated impulse withstand voltage.
The 1SDA070448R1 is a four-pole switch-disconnector in a fixed configuration with front terminals.
It is intended for photovoltaic power systems, high-power DC distribution, solar inverter installations and other high-current DC switching and isolation applications.
ABB Tmax T-D/PV switch-disconnectors provide robust switching and isolation solutions for demanding photovoltaic, renewable-energy and high-power DC electrical installations.{ "@context": "https://schema.org", "@type": "Product", "name": "ABB 1SDA070448R1 T7N-D/PV 1000 MCS UL 4-Pole 1000 V DC Switch-Disconnector", "brand": { "@type": "Brand", "name": "ABB" }, "mpn": "1SDA070448R1", "gtin13": "8015644714949", "description": "ABB 1SDA070448R1 is a T7N-D/PV 1000 MCS UL four-pole fixed switch-disconnector with front terminals and stored-energy operation, rated at 1000 A and 1000 V DC for high-power photovoltaic and DC applications.", "category": "Switch-Disconnectors", "additionalProperty": [ { "@type": "PropertyValue", "name": "Rated Current", "value": "1000 A" }, { "@type": "PropertyValue", "name": "Rated Voltage", "value": "1000 V DC" }, { "@type": "PropertyValue", "name": "Number of Poles", "value": "4" }, { "@type": "PropertyValue", "name": "Short-Time Withstand Current", "value": "18 kA for 1 s" }, { "@type": "PropertyValue", "name": "Impulse Withstand Voltage", "value": "8 kV" }, { "@type": "PropertyValue", "name": "Dimensions", "value": "268 × 280 × 178 mm" }, { "@type": "PropertyValue", "name": "Weight", "value": "17.5 kg" } ] } { "@context": "https://schema.org", "@type": "FAQPage", "mainEntity": [ { "@type": "Question", "name": "What is the ABB 1SDA070448R1?", "acceptedAnswer": { "@type": "Answer", "text": "The ABB 1SDA070448R1 is a T7N-D/PV 1000 MCS UL four-pole fixed switch-disconnector with front terminals and a stored-energy operating mechanism for 1000 V DC applications." } }, { "@type": "Question", "name": "What current is the ABB 1SDA070448R1 rated for?", "acceptedAnswer": { "@type": "Answer", "text": "The ABB 1SDA070448R1 has a rated uninterrupted current of 1000 A." } }, { "@type": "Question", "name": "What voltage can the ABB 1SDA070448R1 handle?", "acceptedAnswer": { "@type": "Answer", "text": "The device has a rated operational voltage and rated insulation voltage of 1000 V DC, with an 8 kV rated impulse withstand voltage." } }, { "@type": "Question", "name": "How many poles does the ABB 1SDA070448R1 have?", "acceptedAnswer": { "@type": "Answer", "text": "The 1SDA070448R1 is a four-pole switch-disconnector in a fixed configuration with front terminals." } }, { "@type": "Question", "name": "Where is the ABB 1SDA070448R1 typically used?", "acceptedAnswer": { "@type": "Answer", "text": "It is intended for photovoltaic power systems, high-power DC distribution, solar inverter installations and other high-current DC switching and isolation applications." } } ] }
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.