1SDA104616R1 ABB E6.2H/E9 5000 Ekip Dip LSIG 4p FHR 900V Air Circuit Breaker

1SDA104616R1 ABB E6.2H/E9 5000 Ekip Dip LSIG 4p FHR 900V Air Circuit Breaker

ABB 1SDA104616R1 SACE Emax 2 E6.2H/E9 four-pole fixed air circuit breaker with a 5000 A rated current, Ekip Dip LSIG electronic protection, rear flat horizontal terminals and 75 kA breaking capacity at 900 V AC.

SKU: 1SDA104616R1MPN: 1SDA104616R1
Price
List Price £43,725.53 ex VAT
Your Price (ex VAT) Save 25%
£32,794.15 25% OFF
You save £10,931.38 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £32,794.15
Trade pricing is personalised to your account

Manufacturer Lead Time

£32,794.15

Why Choose the ABB E6.2H/E9 5000 Ekip Dip LSIG 4p FHR 900V Air Circuit Breaker?

The ABB 1SDA104616R1 is a high-capacity SACE Emax 2 air circuit breaker (ACB) engineered for protection and switching in demanding electrical distribution systems operating at 900 V AC. This E6.2H/E9 model combines a 5000 A rated uninterrupted current, four-pole construction and ABB's Ekip Dip LSIG electronic trip unit, making it suitable for major industrial, infrastructure and energy distribution applications.

The Ekip Dip LSIG solid-state electronic protection release provides long-time, short-time, instantaneous and ground-fault protection. These functions enable the breaker to protect high-current circuits against sustained overloads, short circuits and earth faults while supporting effective protection coordination throughout the electrical distribution system.

The 1SDA104616R1 is a fixed four-pole circuit breaker with rear flat horizontal (FHR) terminals, providing a robust arrangement for permanent switchboard and busbar installation. Its E6.2H performance level delivers an ultimate short-circuit breaking capacity of 75 kA at 900 V AC, providing substantial fault-interruption capability for high-power electrical installations.

Key Advantages

  • High-capacity ABB SACE Emax 2/E9 air circuit breaker for demanding power distribution systems.
  • 5000 A rated uninterrupted current for substantial industrial and infrastructure loads.
  • Designed for electrical networks operating at 900 V AC.
  • 75 kA ultimate short-circuit breaking capacity at 900 V AC for high fault-current applications.
  • Four-pole configuration supports switching of three phases and neutral.
  • Ekip Dip LSIG electronic trip unit provides comprehensive overload, short-circuit and ground-fault protection.
  • Rear flat horizontal terminals support fixed switchboard and busbar integration.
  • Electronic protection settings support effective selectivity and coordination within complex distribution systems.

Key Features

  • ABB SACE Emax 2 E6.2H/E9 series.
  • 5000 A rated uninterrupted current (Iu).
  • 900 V AC rated operational voltage.
  • 75 kA ultimate short-circuit breaking capacity (Icu) at 900 V AC.
  • 4-pole configuration.
  • Ekip Dip LSIG solid-state electronic protection release.
  • Long-time (L), short-time (S), instantaneous (I) and ground-fault (G) protection functions.
  • 2000–5000 A overload protection adjustment range.
  • Integrated ground-fault protection.
  • 4 auxiliary contacts for signalling and control functions.
  • Circuit-breaker open/closed position indication.
  • Fixed execution for permanent switchboard installation.
  • Rear flat horizontal (FHR) terminals with bolted main-circuit connection.

High-Current LSIG Protection for 900 V Power Distribution

Air circuit breakers such as the ABB SACE Emax 2 E6.2H/E9 provide switching and protection for high-current electrical distribution systems where substantial prospective fault currents can occur. The Ekip Dip electronic release monitors circuit current and operates the breaker according to configured protection thresholds, helping safeguard busbars, conductors, switchgear and downstream equipment from damaging electrical faults.

The LSIG protection package combines long-time protection against sustained overloads, short-time protection for selective fault coordination, instantaneous protection against severe short circuits and ground-fault protection for earth-fault conditions. Together with its 5000 A current rating, 75 kA breaking capacity at 900 V AC, four-pole construction and fixed rear-terminal arrangement, the 1SDA104616R1 provides a robust solution for critical high-power distribution switchboards.

Typical Applications

  • High-current industrial 900 V AC power distribution systems.
  • Main incomer and distribution circuit protection.
  • Industrial switchboards and power distribution centres.
  • Manufacturing and process industry electrical systems.
  • Power generation and energy infrastructure.
  • High-power machinery and plant electrical supplies.
  • Four-pole electrical systems requiring neutral switching.
  • Systems requiring overload, short-circuit and ground-fault protection.
  • Fixed switchgear installations using rear horizontal busbar connections.

Technical Specifications

Tick the specs you need, then view products that match.

Voltage 900 V AC
Device Type ACB
Series SACE Emax 2
Order code 1SDA104616R1
Product type Air circuit breaker
Frame E6.2
Short-circuit performance level H
Rated uninterrupted current (Iu) 5000 A
Overload protection adjustment range 2000–5000 A
Rated operational voltage 900 V AC
Ultimate short-circuit breaking capacity (Icu) at 900 V AC 75 kA
Number of poles 4
Current type AC
Trip unit Ekip Dip LSIG
Release type Solid-state electronic
Protection functions LSIG – long-time, short-time, instantaneous and ground-fault
Integrated ground-fault protection Yes
Execution Fixed
Terminal connection Rear flat horizontal (FHR)
Main circuit connection Bolted connection
Connection position Rear
Auxiliary contacts 4
Circuit-breaker position indication Open / closed
Product net weight Approximately 125 kg
Product group Emax 2 Air Circuit Breaker

Frequently Asked Questions

What is the ABB 1SDA104616R1 used for?

The ABB 1SDA104616R1 is an Emax 2/E9 air circuit breaker designed for switching and protecting high-current electrical distribution systems against overload, short-circuit and ground-fault conditions at 900 V AC.

What is the current rating of the ABB 1SDA104616R1?

The E6.2H/E9 breaker has a rated uninterrupted current of 5000 A, with an overload protection adjustment range of 2000–5000 A.

What protection functions does the Ekip Dip LSIG trip unit provide?

The Ekip Dip LSIG electronic trip unit provides long-time (L), short-time (S), instantaneous (I) and ground-fault (G) protection against sustained overloads, short circuits and earth faults.

What is the breaking capacity of the E6.2H/E9 5000 at 900 V AC?

The E6.2H/E9 5000 has an ultimate short-circuit breaking capacity of 75 kA at 900 V AC, providing substantial fault-interruption capability for demanding high-current electrical distribution systems.

Is the ABB 1SDA104616R1 a fixed or withdrawable circuit breaker?

The 1SDA104616R1 is a four-pole fixed air circuit breaker with rear flat horizontal (FHR) terminals, designed for permanent installation and rear busbar connection within compatible switchgear assemblies.

Trusted Protection from ABB Emax 2

ABB SACE Emax 2 air circuit breakers combine advanced electronic protection with high short-circuit performance and flexible switchgear integration, providing dependable circuit protection for demanding industrial, infrastructure and energy distribution applications.