ABB 1SDA104615R1 SACE Emax 2 E6.2H/E9 four-pole fixed air circuit breaker with a 5000 A rated current, Ekip Dip LSI electronic protection, rear flat horizontal terminals and 75 kA breaking capacity at 900 V AC.
£32,233.36
The ABB 1SDA104615R1 is a high-capacity SACE Emax 2 air circuit breaker (ACB) engineered for protection and switching in demanding low-voltage electrical distribution systems operating at 900 V AC. This E6.2H/E9 model combines a 5000 A rated uninterrupted current, four-pole construction and ABB's Ekip Dip LSI electronic trip unit, making it suitable for major industrial, infrastructure and energy distribution applications.
The Ekip Dip LSI electronic protection release provides long-time, short-time and instantaneous overcurrent protection. Its adjustable protection functions enable the breaker to protect high-current circuits against sustained overloads and short-circuit faults while supporting coordination with other protective devices within the electrical distribution system.
Unlike withdrawable Emax 2 variants, the 1SDA104615R1 is a fixed circuit breaker with rear flat horizontal (FHR) terminals. The E6.2H performance level provides both an ultimate and service short-circuit breaking capacity of 75 kA at 900 V AC, giving the breaker substantial fault-interruption capability for high-power installations.
Air circuit breakers such as the ABB SACE Emax 2 E6.2H/E9 provide protection and switching for high-current electrical distribution systems where substantial fault levels can occur. The Ekip Dip electronic trip unit monitors circuit current and operates the breaker according to configured protection thresholds, helping safeguard busbars, conductors, switchgear and downstream electrical equipment against overload and short-circuit conditions.
The LSI protection package combines long-time protection against sustained overloads, short-time protection to support selective fault coordination and instantaneous protection against severe short circuits. Together with its 5000 A current rating, 75 kA Icu and Ics at 900 V AC, four-pole construction and fixed rear-terminal configuration, the 1SDA104615R1 provides a robust solution for high-power distribution switchboards.
Tick the specs you need, then view products that match.
| Voltage | 900 V AC | |
|---|---|---|
| Device Type | ACB | |
| Series | SACE Emax 2 | |
| Order code | 1SDA104615R1 | |
| Product type | Air circuit breaker | |
| Frame | E6.2 | |
| Short-circuit performance level | H | |
| Rated current (In) | 5000 A | |
| Rated uninterrupted current (Iu) | 5000 A | |
| Rated operational voltage (Ue) | 900 V AC | |
| Rated voltage (Ur) | 900 V | |
| Rated insulation voltage (Ui) | 1000 V AC | |
| Rated impulse withstand voltage (Uimp) | 12 kV | |
| Ultimate short-circuit breaking capacity (Icu) at 900 V AC | 75 kA | |
| Service short-circuit breaking capacity (Ics) at 900 V AC | 75 kA | |
| Short-time withstand current (Icw), 1 s | 75 kA | |
| Short-time withstand current (Icw), 3 s | 66 kA | |
| Number of poles | 4 | |
| Current type | AC | |
| Trip unit | Ekip Dip LSI | |
| Release type | Electronic | |
| Protection functions | LSI – long-time, short-time and instantaneous | |
| Overload release current setting | 2000 A | |
| Short-time delayed short-circuit release setting | 3000 A | |
| Instantaneous short-circuit release setting | 7500 A | |
| Integrated earth-fault protection | No | |
| Execution | Fixed | |
| Terminal connection | Rear flat horizontal (FHR) | |
| Main circuit connection | Bolt connection | |
| Connection position | Rear | |
| Auxiliary changeover contacts | 4 | |
| Trip / switched-off indication | Yes | |
| Integrated motor operator | No | |
| Optional motor operator | Yes | |
| Integrated undervoltage release | No | |
| Degree of protection | IP30 | |
| Electrical durability at 900 V | 1000 cycles | |
| Electrical operating frequency | 10 cycles per hour | |
| Mechanical durability | 12000 cycles | |
| Mechanical operating frequency | 60 cycles per hour | |
| Power loss | 483 W | |
| Product net width | 888 mm | |
| Product net height | 371 mm | |
| Product net depth | 270 mm | |
| Product net weight | 125 kg | |
| Standard | IEC 60947-2 | |
| Product group | Emax 2 Air Circuit Breaker |
The ABB 1SDA104615R1 is an Emax 2/E9 air circuit breaker designed for switching and protecting high-current electrical distribution systems against overload and short-circuit conditions at 900 V AC.
The E6.2H/E9 breaker has a rated current and rated uninterrupted current of 5000 A, making it suitable for substantial industrial, infrastructure and energy distribution loads.
The Ekip Dip LSI electronic trip unit provides long-time (L), short-time (S) and instantaneous (I) protection against sustained overloads and short-circuit faults.
The E6.2H/E9 5000 has an ultimate short-circuit breaking capacity (Icu) and service short-circuit breaking capacity (Ics) of 75 kA at 900 V AC.
The 1SDA104615R1 is a four-pole fixed air circuit breaker with rear flat horizontal (FHR) terminals, designed for permanent installation and rear busbar connection within compatible switchgear assemblies.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection with high short-circuit performance and flexible switchgear integration, providing dependable circuit protection for demanding industrial, infrastructure and energy distribution applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.