Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA104520R1 Emax 2 E4.2H/E9 three-pole withdrawable air circuit breaker with a 3200 A rated current, Ekip Hi-Touch LSIG electronic protection and 75 kA ultimate and service breaking capacity at 900 V AC.
£20,549.67
The ABB 1SDA104520R1 is a high-performance Emax 2 air circuit breaker (ACB) engineered for protection, control and switching in demanding electrical distribution systems operating at 900 V AC. This E4.2H/E9 model combines a 3200 A rated uninterrupted current, three-pole configuration and ABB's advanced Ekip Hi-Touch LSIG electronic trip unit for comprehensive protection of high-current industrial, infrastructure and energy installations.
The Ekip Hi-Touch LSIG electronic release provides long-time, short-time, instantaneous and ground-fault protection, together with advanced monitoring and protection capabilities for sophisticated power distribution systems. Its configurable electronic protection helps engineers coordinate protection settings while safeguarding equipment against overloads, short circuits and earth faults.
Designed as a withdrawable moving part (WMP), the E4.2H/E9 3200 supports efficient inspection, maintenance and replacement in compatible ABB Emax 2 switchgear. The H short-circuit performance level delivers both an ultimate and service short-circuit breaking capacity of 75 kA at 900 V AC, making the 1SDA104520R1 suitable for installations with demanding prospective fault-current requirements.
Air circuit breakers such as the ABB Emax 2 E4.2H/E9 are designed to protect high-current electrical distribution systems against damaging overloads, short circuits and earth faults. The Ekip Hi-Touch electronic trip unit continuously supports protection functions based on configured operating thresholds, allowing the breaker to disconnect a circuit when abnormal electrical conditions require protective intervention.
The LSIG functionality combines long-time protection against sustained overloads, short-time protection for selective fault coordination, instantaneous protection against severe short circuits and ground-fault protection for earth-fault conditions. Together with a 3200 A current rating, 75 kA Icu and Ics at 900 V AC and withdrawable Emax 2 architecture, the 1SDA104520R1 provides a powerful protection solution for critical high-energy switchboards.
Tick the specs you need, then view products that match.
| Voltage | 900 V AC | |
|---|---|---|
| Device Type | ACB | |
| Series | SACE Emax 2 | |
| Order code | 1SDA104520R1 | |
| Product type | Air circuit breaker | |
| Frame | E4.2 | |
| Short-circuit performance level | H | |
| Rated current (In) | 3200 A | |
| Rated uninterrupted current (Iu) | 3200 A | |
| Rated operational voltage | 900 V AC | |
| Rated insulation voltage (Ui) | 1000 V AC | |
| Rated impulse withstand voltage (Uimp) | 12 kV | |
| Ultimate short-circuit breaking capacity (Icu) at 900 V AC | 75 kA | |
| Service short-circuit breaking capacity (Ics) at 900 V AC | 75 kA | |
| Short-time withstand current (Icw), 1 s | 75 kA | |
| Short-time withstand current (Icw), 3 s | 66 kA | |
| Number of poles | 3 | |
| Current type | AC | |
| Trip unit | Ekip Hi-Touch LSIG | |
| Release type | Electronic | |
| Protection functions | LSIG – long-time, short-time, instantaneous and ground-fault | |
| Overload release current setting | 1280 A | |
| Short-time delayed short-circuit release setting | 1920 A | |
| Instantaneous short-circuit release setting | 4800 A | |
| Integrated earth-fault protection | Yes | |
| Auxiliary changeover contacts | 4 | |
| Degree of protection | IP30 | |
| Terminal connection | Rear flat horizontal | |
| Main circuit connection | Connection at separate chassis part | |
| Execution | Withdrawable moving part (WMP) | |
| Electrical durability at 900 V | 1000 cycles | |
| Electrical operating frequency | 10 cycles per hour | |
| Mechanical durability | 20000 cycles | |
| Mechanical operating frequency | 60 cycles per hour | |
| Power loss | 743 W | |
| Motor drive integrated | No | |
| Motor drive optional | Yes | |
| Integrated undervoltage release | No | |
| Switched-off indication | Yes | |
| Standard | IEC 60947-2 | |
| Product group | Emax 2 Air Circuit Breaker |
The ABB 1SDA104520R1 is an Emax 2/E9 air circuit breaker designed for switching and protecting high-current electrical distribution systems against overload, short-circuit and ground-fault conditions at 900 V AC.
The E4.2H/E9 breaker has a rated current and rated uninterrupted current of 3200 A, making it suitable for substantial industrial and energy distribution loads.
The Ekip Hi-Touch LSIG electronic trip unit provides long-time (L), short-time (S), instantaneous (I) and ground-fault (G) protection against overload, short-circuit and earth-fault conditions.
The E4.2H/E9 3200 has both an ultimate short-circuit breaking capacity (Icu) and service short-circuit breaking capacity (Ics) of 75 kA at 900 V AC.
Yes. The 1SDA104520R1 is a three-pole withdrawable moving part (WMP) designed for use with a compatible ABB Emax 2 chassis, supporting efficient servicing and replacement within the switchgear assembly.
ABB SACE Emax 2 air circuit breakers combine advanced electronic protection with high short-circuit performance and flexible switchgear integration, providing dependable circuit protection for demanding industrial, infrastructure and energy distribution applications.
We use cookies