ABB 1SDA104483R1 Emax 2 E2.2H/E9 four-pole withdrawable air circuit breaker with a 1250 A rated current, Ekip Dip LSIG electronic protection and 65 kA breaking capacity at 900 V AC.
£8,831.42
The ABB 1SDA104483R1 is a high-performance Emax 2 air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems operating at up to 900 V AC. Part of the advanced ABB Emax 2 series, this E2.2H breaker combines a 1250 A rated uninterrupted current, four-pole configuration and Ekip Dip LSIG electronic trip unit for comprehensive protection of industrial, commercial and infrastructure power networks.
The breaker incorporates ABB's Ekip Dip LSIG electronic protection trip unit, providing long-time, short-time, instantaneous and ground-fault protection. These functions help protect electrical installations against overloads, short circuits and earth faults while supporting selective coordination across power distribution systems.
Designed as a withdrawable moving part (WMP) for Emax 2 switchgear, the E2.2H/E9 1250 facilitates inspection, servicing and replacement in compatible withdrawable assemblies. Its H short-circuit performance level provides an ultimate short-circuit breaking capacity of 65 kA at 900 V AC, making it particularly suitable for installations requiring high fault-current performance.
Air circuit breakers such as the ABB Emax 2 E2.2H are designed to protect high-current low-voltage electrical distribution systems against potentially damaging electrical faults. The Ekip Dip electronic trip unit monitors current and initiates breaker operation when configured protection thresholds are exceeded, helping protect conductors, equipment and downstream electrical loads.
The LSIG protection functions provide long-time protection against sustained overloads, short-time protection for selective short-circuit coordination, instantaneous protection against severe fault currents and ground-fault protection for earth-fault conditions. Combined with the E2.2H's 65 kA breaking capacity at 900 V AC and withdrawable Emax 2 architecture, the 1SDA104483R1 is well suited to critical switchboards where high fault-current performance, serviceability and system continuity are important.
Tick the specs you need, then view products that match.
| Voltage | 900 V AC | |
|---|---|---|
| Device Type | ACB | |
| Series | SACE Emax 2 | |
| Order code | 1SDA104483R1 | |
| Product type | Air circuit breaker | |
| Frame / sub-type | E2.2 | |
| Short-circuit performance level | H | |
| Rated uninterrupted current (Iu) | 1250 A | |
| Rated current (In) | 1250 A | |
| Rated operational voltage | 900 V AC | |
| Rated insulation voltage (Ui) | 1000 V AC | |
| Rated impulse withstand voltage (Uimp) | 12 kV | |
| Ultimate short-circuit breaking capacity (Icu) at 900 V AC | 65 kA | |
| Service short-circuit breaking capacity (Ics) at 900 V AC | 65 kA | |
| Short-time withstand current (Icw) | 65 kA for 1 s / 3 s | |
| Number of poles | 4 | |
| Current type | AC | |
| Trip unit | Ekip Dip LSIG | |
| Release type | Electronic | |
| Protection functions | LSIG – long-time, short-time, instantaneous and ground-fault | |
| Execution | Withdrawable moving part (WMP) | |
| Terminal connection | Rear flat horizontal | |
| Electrical durability | 2000 cycles at 900 V | |
| Mechanical durability | 25,000 cycles | |
| Power loss | 176 W | |
| Suitable for IT networks | Yes, at 900 V | |
| Standard | IEC 60947-2 | |
| Weight | approx. 49 kg | |
| Product group | Emax 2 Air Circuit Breaker |
The ABB 1SDA104483R1 is an Emax 2 air circuit breaker used for switching and protecting high-current low-voltage electrical distribution systems against overload, short-circuit and ground-fault conditions.
The E2.2H/E9 breaker has a rated uninterrupted current of 1250 A.
The Ekip Dip LSIG trip unit provides long-time (L), short-time (S), instantaneous (I) and ground-fault (G) protection for comprehensive protection against overload, short-circuit and earth-fault conditions.
The E2.2H version has an ultimate short-circuit breaking capacity of 65 kA at 900 V AC, with a rated service short-circuit breaking capacity of 65 kA at the same voltage.
Yes. The 1SDA104483R1 is a four-pole withdrawable moving part (WMP) designed for installation in compatible ABB Emax 2 withdrawable switchgear assemblies.
ABB Emax 2 air circuit breakers are engineered for dependable protection and control of low-voltage electrical distribution systems, combining advanced electronic protection with high short-circuit performance and flexible switchgear integration for industrial, commercial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.