ABB 1SDA104371R1 is a fixed four-pole SACE Emax 2 E2.2H/E9 2000 A air circuit breaker with horizontal rear terminals, Ekip Touch LSI electronic protection and a 65 kA ultimate short-circuit breaking capacity at 900 V AC.

SKU: 1SDA104371R1MPN: 1SDA104371R1
Price
List Price £15,324.59 ex VAT
Your Price (ex VAT) Save 25%
£11,493.44 25% OFF
You save £3,831.15 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,493.44
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,493.44

Why Choose the ABB E2.2H/E9 2000 Ekip Touch LSI 4p FHR 900V?

The ABB E2.2H/E9 2000 Ekip Touch LSI 4p FHR 900V, order code 1SDA104371R1, is a high-performance SACE Emax 2 air circuit breaker designed for switching and protection in demanding low-voltage AC power distribution systems. Built on the E2.2 frame, this fixed four-pole breaker combines a rated uninterrupted current of 2000 A with ABB's advanced Ekip Touch LSI electronic protection release.

The Ekip Touch LSI trip unit provides electronic protection covering long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) functions. Its touch-based interface and configurable electronic protection architecture make it well suited to high-current installations requiring advanced overcurrent protection, measurement and power-system supervision.

This E2.2H/E9 configuration is designed for 900 V AC applications and features a fixed four-pole construction with horizontal rear terminals (FHR). The H performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 900 V AC, while the four-pole arrangement supports three-phase systems where switching of the neutral conductor is required.

Key Advantages

  • High-performance ABB SACE Emax 2 E2.2 air circuit breaker.
  • 2000 A rated uninterrupted current for high-current power distribution.
  • Designed for 900 V AC applications.
  • High 65 kA ultimate short-circuit breaking capacity at 900 V AC.
  • Advanced Ekip Touch LSI electronic protection against overload and short-circuit conditions.
  • Four-pole fixed construction with horizontal rear terminals for permanent integration into compatible switchboards.

Key Features

  • ABB SACE Emax 2 E2.2 frame.
  • H high short-circuit performance level.
  • 2000 A rated uninterrupted current (Iu).
  • 900 V AC configuration.
  • Four-pole construction.
  • Ekip Touch LSI electronic protection release.
  • Long-time overload protection (L).
  • Short-time short-circuit protection (S).
  • Instantaneous short-circuit protection (I).
  • Fixed-mounted construction.
  • Horizontal rear terminal arrangement (FHR).
  • Four auxiliary contacts (4Q) for breaker status signalling.
  • Trip signalling contact (S51).
  • High 65 kA breaking performance at 900 V AC.

High-Breaking-Capacity Ekip Touch Protection for Emax 2

ABB SACE Emax 2 air circuit breakers provide switching and protection for high-current low-voltage distribution circuits. The E2.2H/E9 configuration combines a substantial 2000 A current rating with an H-level ultimate short-circuit breaking capacity of 65 kA at 900 V AC, making it particularly suitable for electrical systems where both high load currents and high prospective fault currents must be managed reliably.

The Ekip Touch LSI release gives the 1SDA104371R1 long-time overload, short-time short-circuit and instantaneous short-circuit protection. Combined with its fixed four-pole construction and horizontal rear terminals, this configuration provides a robust solution for industrial, infrastructure and power distribution switchboards requiring advanced electronic overcurrent protection and high breaking performance.

Typical Applications

  • Main low-voltage power distribution switchboards.
  • Three-phase four-wire distribution systems.
  • High-current transformer incomers and feeders.
  • Generator and power generation distribution systems.
  • Industrial manufacturing and process facilities.
  • High-fault-level systems requiring 2000 A capacity and 65 kA breaking performance at 900 V AC.

Technical Specifications

Tick the specs you need, then view products that match.

Voltage 900 V AC
Device Type ACB
Series SACE Emax 2
Frame size E2.2
Order code 1SDA104371R1
Product type Air circuit breaker
Short-circuit performance level H
Rated uninterrupted current (Iu) 2000 A
Application voltage 900 V AC
Rated ultimate short-circuit breaking capacity (Icu) 65 kA at 900 V AC
Number of poles 4
Protection release Ekip Touch LSI
Release type Electronic
Protection functions L, S, I
Installation Fixed
Main-circuit connection Bolt connection
Connection position Rear
Terminal configuration Fixed horizontal rear (FHR)
Auxiliary contacts 4Q
Trip signalling contact S51
DIN-rail mounting No

Frequently Asked Questions

What is the ABB 1SDA104371R1?

The ABB 1SDA104371R1 is a four-pole fixed SACE Emax 2 E2.2H/E9 air circuit breaker rated at 2000 A, designed for 900 V AC applications and equipped with an Ekip Touch LSI electronic protection release.

What protection functions does the Ekip Touch LSI release provide?

The Ekip Touch LSI release provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.

What is the breaking capacity of the ABB 1SDA104371R1?

The ABB 1SDA104371R1 has a rated ultimate short-circuit breaking capacity Icu of 65 kA at 900 V AC.

What does 4p FHR mean on the ABB 1SDA104371R1?

4p identifies a four-pole breaker, while FHR identifies the fixed configuration with horizontal rear terminals for integration with compatible switchboard busbars and conductors.

Does the ABB 1SDA104371R1 include earth-fault protection?

The specified Ekip Touch LSI release provides L, S and I protection functions. It does not include the dedicated G earth-fault protection function provided by Ekip Touch LSIG versions.