Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA104359R1 is a 2500 A three-pole SACE Emax 2 E2.2H/E9 fixed air circuit breaker with horizontal rear terminals, a 900 V AC rating, 65 kA breaking capacity and an Ekip Touch LSIG electronic trip unit.
£12,631.24
The ABB 1SDA104359R1 is a SACE Emax 2 E2.2H/E9 air circuit breaker rated at 2500 A and 900 V AC. This three-pole fixed breaker combines the high-performance E2.2H/E9 frame with an Ekip Touch LSIG electronic trip unit and horizontal rear main terminals for demanding high-current power distribution applications.
The Ekip Touch LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. Its touch-display interface gives operators convenient access to protection settings and electrical information, while the Ekip platform supports expansion with compatible ABB measurement, signalling and communication accessories.
With an ultimate and service short-circuit breaking capacity of 65 kA at 900 V AC, the E2.2H/E9 configuration is designed for installations requiring substantial fault-interruption capability. The fixed horizontal rear (FHR) arrangement provides rear-facing main connections for integration with compatible switchboard busbars and conductors.
The Ekip Touch LSIG electronic trip unit combines four key protection functions. Long-time protection responds to sustained overloads, short-time protection provides controlled response to high fault currents, instantaneous protection rapidly interrupts severe short circuits, and the G function provides dedicated earth-fault protection. The touch-display interface also provides direct access to settings and operating information.
Combined with the E2.2H/E9 2500 A platform and its 65 kA breaking capacity at 900 V AC, the 1SDA104359R1 provides high-performance protection for demanding power distribution systems. ABB also specifies this breaker in reference architectures for high-power photovoltaic AC distribution, demonstrating its suitability for modern high-voltage low-voltage installations.
Tick the specs you need, then view products that match.
| Voltage | 900 V AC | |
|---|---|---|
| Device Type | ACB | |
| Series | SACE Emax 2 | |
| Frame | E2.2H/E9 | |
| ABB order code | 1SDA104359R1 | |
| Product designation | E2.2H/E9 2500 Ekip Touch LSIG 3p FHR 900V | |
| Product type | Air circuit breaker | |
| Rated uninterrupted current (Iu) | 2500 A | |
| Rated operational voltage (Ue) | 900 V AC | |
| Rated insulation voltage (Ui) | 1000 V AC | |
| Rated impulse withstand voltage (Uimp) | 12 kV | |
| Number of poles | 3 | |
| Trip unit | Ekip Touch LSIG | |
| Release type | Electronic | |
| Protection functions | L, S, I, G | |
| Overload release current setting | From 1000 A | |
| Short-time delayed short-circuit setting | From 1500 A | |
| Instantaneous short-circuit setting | From 3750 A | |
| Integrated earth-fault protection | Yes | |
| Rated ultimate short-circuit breaking capacity (Icu) at 900 V AC | 65 kA | |
| Rated service short-circuit breaking capacity (Ics) at 900 V AC | 65 kA | |
| Rated short-time withstand current (Icw), 1 s | 65 kA | |
| Rated short-time withstand current (Icw), 3 s | 65 kA | |
| Installation | Fixed | |
| Main-circuit connection | Bolt connection | |
| Terminal position | Rear | |
| Terminal arrangement | Horizontal rear | |
| Auxiliary contacts | 4 changeover contacts | |
| Switched-off indication | Yes | |
| Integrated motor drive | No | |
| Optional motor drive | Yes | |
| Suitable for IT networks | Yes, 900 V | |
| Degree of protection | IP30 | |
| Power loss | 267 W | |
| Product net dimensions (W × H × D) | 276 × 371 × 270 mm | |
| Product net weight | 41 kg | |
| EAN | 8015644064396 | |
| Standard | IEC | |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA104359R1 is an Emax 2 E2.2H/E9 2500 A three-pole fixed air circuit breaker with horizontal rear terminals, a 900 V AC rating and an Ekip Touch LSIG electronic trip unit.
The LSIG configuration provides long-time overload protection (L), short-time delayed short-circuit protection (S), instantaneous short-circuit protection (I) and earth-fault protection (G).
The ABB 1SDA104359R1 has a rated uninterrupted current of 2500 A.
The E2.2H/E9 1SDA104359R1 has a rated operational voltage of 900 V AC and a rated insulation voltage of 1000 V AC.
The breaker has an ultimate short-circuit breaking capacity Icu of 65 kA at 900 V AC and a service short-circuit breaking capacity Ics of 65 kA at 900 V AC.
Yes. The G function of the Ekip Touch LSIG trip unit provides integrated earth-fault protection.
FHR identifies a fixed breaker with horizontal rear terminals, providing rear-facing main-circuit connections for compatible switchboard busbars or conductors.
Yes. ABB specifies the E2.2H/E9 1SDA104359R1 as suitable for 900 V IT networks.
Yes. ABB includes the 1SDA104359R1 in reference architectures for high-power photovoltaic installations, including AC re-combiner applications.
ABB SACE Emax 2 air circuit breakers combine high-current switching, advanced electronic protection and flexible digital connectivity to support dependable power distribution in industrial, infrastructure and renewable-energy installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.