Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA104348R1 is a fixed three-pole SACE Emax 2 E2.2H/E9 1250 A air circuit breaker with horizontal rear terminals, Ekip Dip LSIG electronic protection and a 65 kA ultimate short-circuit breaking capacity at 900 V AC.
£7,232.55
The ABB E2.2H/E9 1250 Ekip Dip LSIG 3p FHR 900V, order code 1SDA104348R1, is a high-performance SACE Emax 2 air circuit breaker designed for switching and protection in demanding low-voltage AC power distribution systems. Built on the E2.2 frame, this fixed three-pole breaker combines a rated uninterrupted current of 1250 A with ABB's Ekip Dip LSIG electronic protection release.
The Ekip Dip LSIG trip unit provides electronic protection covering long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground or earth-fault (G) functions. This combination provides comprehensive protection against common distribution-system faults while retaining the straightforward configuration associated with ABB's Ekip Dip platform.
This E2.2H/E9 configuration is designed for 900 V AC applications and features a fixed three-pole construction with horizontal rear terminals (FHR). The H performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 900 V AC, making the breaker particularly suitable for installations with high prospective fault currents.
ABB SACE Emax 2 air circuit breakers provide switching and protection for high-current low-voltage distribution circuits. The E2.2H/E9 configuration combines a 1250 A current rating with an H-level ultimate breaking capacity of 65 kA at 900 V AC, providing robust fault interruption for electrical systems with high prospective short-circuit currents.
The Ekip Dip LSIG release gives the 1SDA104348R1 long-time overload, short-time short-circuit, instantaneous short-circuit and ground or earth-fault protection. Combined with its fixed E2.2 construction and horizontal rear terminals, this configuration provides a dependable solution for permanent installation in industrial, infrastructure and power distribution switchboards requiring comprehensive LSIG protection.
Tick the specs you need, then view products that match.
| Voltage | 900 V AC | |
|---|---|---|
| Device Type | ACB | |
| Series | SACE Emax 2 | |
| Frame size | E2.2 | |
| Order code | 1SDA104348R1 | |
| Product type | Air circuit breaker | |
| Short-circuit performance level | H | |
| Rated uninterrupted current (Iu) | 1250 A | |
| Rated voltage | 900 V AC | |
| Rated ultimate short-circuit breaking capacity (Icu) | 65 kA at 900 V AC | |
| Overload release current setting | 1250 A | |
| Short-time delayed short-circuit release setting | 12500 A | |
| Instantaneous short-circuit release setting | 1875 A | |
| Number of poles | 3 | |
| Protection release | Ekip Dip LSIG | |
| Release type | Electronic | |
| Protection functions | L, S, I, G | |
| Integrated earth-fault protection | Yes | |
| Installation | Fixed | |
| Main-circuit connection | Bolt connection | |
| Connection position | Rear | |
| Terminal configuration | Fixed horizontal rear (FHR) | |
| Auxiliary contacts | 4 change-over contacts | |
| Open/closed position indication | Yes | |
| Control element | Push button | |
| Motor drive integrated | No | |
| Motor drive optional | Yes | |
| Protection rating | IP30 | |
| DIN-rail mounting | No | |
| Net weight | 41 kg |
The ABB 1SDA104348R1 is a three-pole fixed SACE Emax 2 E2.2H/E9 air circuit breaker rated at 1250 A and 900 V AC, equipped with an Ekip Dip LSIG electronic protection release.
The Ekip Dip LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground or earth-fault (G) protection.
The E2.2H/E9 1SDA104348R1 has a rated ultimate short-circuit breaking capacity Icu of 65 kA at 900 V AC.
3p identifies a three-pole breaker, while FHR identifies the fixed configuration with horizontal rear terminals for connection to compatible switchboard busbars or conductors.
Yes. The G function of the Ekip Dip LSIG release provides integrated earth-fault protection alongside long-time, short-time and instantaneous overcurrent protection.
ABB SACE Emax 2 air circuit breakers combine high-current switching, electronic protection and high short-circuit breaking performance, while Ekip Dip LSIG technology provides comprehensive overload, short-circuit and earth-fault protection for demanding low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.