ABB 1SDA104333R1 is a fixed four-pole SACE Emax 2 E2.2S/E9 1250 A air circuit breaker with horizontal rear terminals, a 900 V AC rating and Ekip Dip LSIG electronic protection.

SKU: 1SDA104333R1MPN: 1SDA104333R1
Price
List Price £10,652.69 ex VAT
Your Price (ex VAT) Save 25%
£7,989.52 25% OFF
You save £2,663.17 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,989.52
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,989.52

Why Choose the ABB E2.2S/E9 1250 Ekip Dip LSIG 4p FHR 900V?

The ABB E2.2S/E9 1250 Ekip Dip LSIG 4p FHR 900V, order code 1SDA104333R1, is a SACE Emax 2 air circuit breaker designed for protection and switching in demanding low-voltage AC power distribution systems. Built on the E2.2 frame, this fixed four-pole breaker combines a rated uninterrupted current of 1250 A with ABB's Ekip Dip LSIG electronic protection release.

The Ekip Dip LSIG trip unit provides electronic protection covering long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground or earth-fault (G) functions. This combination provides comprehensive circuit protection for power distribution applications while retaining straightforward configuration through the Ekip Dip protection platform.

This E2.2S/E9 configuration is designed for a rated voltage of 900 V AC and features a fixed four-pole construction with horizontal rear terminals (FHR). The E2.2S performance level provides a rated ultimate short-circuit breaking capacity of 50 kA at 900 V AC, while the four-pole arrangement allows switching and protection of all four conductors in compatible three-phase systems with neutral.

Key Advantages

  • High-performance ABB SACE Emax 2 E2.2 air circuit breaker.
  • 1250 A rated uninterrupted current for high-current distribution systems.
  • Designed for applications with a rated voltage of 900 V AC.
  • Ekip Dip LSIG electronic protection covering overload, short-circuit and earth-fault conditions.
  • Four-pole fixed construction for three-phase systems requiring neutral switching and protection.
  • Horizontal rear terminals provide a practical main-circuit connection arrangement for compatible switchboards.

Key Features

  • ABB SACE Emax 2 E2.2 frame.
  • S short-circuit performance level.
  • 1250 A rated uninterrupted current (Iu).
  • 900 V AC rated voltage.
  • Four-pole configuration.
  • Ekip Dip LSIG electronic protection release.
  • Integrated earth-fault protection.
  • Fixed-mounted construction.
  • Horizontal rear terminal arrangement (FHR).
  • Main-circuit bolt connection.
  • Four change-over auxiliary contacts.
  • Open/closed position indication.
  • Optional motor drive capability.
  • IP30 degree of protection.

Ekip Dip LSIG Protection for Emax 2 Power Distribution

ABB SACE Emax 2 air circuit breakers provide high-current switching and protection for low-voltage power distribution systems. The E2.2S/E9 platform combines the Emax 2 power section with electronic trip technology, allowing circuits to be protected against overloads, short circuits and earth faults in industrial, commercial and infrastructure installations.

The Ekip Dip LSIG release gives the 1SDA104333R1 long-time overload, short-time short-circuit, instantaneous short-circuit and ground or earth-fault protection. Combined with its 1250 A rating, 900 V AC capability, four-pole construction and horizontal rear terminals, the breaker provides a robust fixed solution for compatible high-current distribution switchboards.

Typical Applications

  • Main low-voltage power distribution switchboards.
  • Three-phase four-wire distribution systems.
  • Transformer and installation protection.
  • Generator and power generation systems.
  • Industrial manufacturing and process facilities.
  • Infrastructure and commercial power distribution requiring LSIG protection.

Technical Specifications

Tick the specs you need, then view products that match.

Voltage 900 V AC
Device Type ACB
Series SACE Emax 2
Frame size E2.2
Order code 1SDA104333R1
EAN 8015644064136
Product type Air circuit breaker
Short-circuit performance level S
Rated uninterrupted current (Iu) 1250 A
Rated voltage 900 V AC
Rated ultimate short-circuit breaking capacity (Icu) 50 kA at 900 V AC
Overload release setting 1250 A
Short-time delayed short-circuit release setting Up to 12500 A
Instantaneous short-circuit release setting From 1875 A
Number of poles 4
Protection release Ekip Dip LSIG
Release type Electronic
Protection functions L, S, I, G
Integrated earth-fault protection Yes
Installation Fixed
Main-circuit connection Bolt connection
Connection position Rear
Terminal configuration Fixed horizontal rear (FHR)
Auxiliary contacts 4 change-over contacts
Open/closed position indication Yes
Control element Push button
Motor drive integrated No
Motor drive optional Yes
Protection rating IP30
Net weight Approx. 53 kg

Frequently Asked Questions

What is the ABB 1SDA104333R1?

The ABB 1SDA104333R1 is a four-pole fixed SACE Emax 2 E2.2S/E9 air circuit breaker with a rated uninterrupted current of 1250 A, a 900 V AC rating and an Ekip Dip LSIG electronic protection release.

What protection functions does the Ekip Dip LSIG release provide?

The Ekip Dip LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground or earth-fault (G) protection.

What are the current and voltage ratings of the ABB 1SDA104333R1?

The breaker has a rated uninterrupted current of 1250 A and a rated voltage of 900 V AC.

What does 4p FHR mean on the ABB 1SDA104333R1?

4p identifies a four-pole breaker, while FHR identifies the fixed configuration with horizontal rear terminals for connection to compatible switchboard busbars or conductors.

Does the ABB 1SDA104333R1 provide earth-fault protection?

Yes. The G function of the Ekip Dip LSIG release provides integrated earth-fault protection alongside long-time, short-time and instantaneous overcurrent protection.