Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA104317R1 is a fixed three-pole Emax 2 E2.2S/E9 1250 A air circuit breaker with rear horizontal terminals, 900 V AC operation, 50 kA breaking capacity and an Ekip Dip LSI electronic trip unit.
£5,954.77
The ABB 1SDA104317R1 is a high-performance Emax 2 E2.2S/E9 air circuit breaker designed for switching and protection in demanding low-voltage AC power distribution systems. Rated at 1250 A and 900 V AC, this three-pole fixed circuit breaker combines robust short-circuit performance with an Ekip Dip LSI electronic trip unit.
As part of the advanced ABB SACE Emax 2/E9 series, the E2.2S/E9 is engineered for high-voltage AC applications where reliable protection, isolation and switching are essential. The Ekip Dip LSI release provides long-time, short-time and instantaneous protection functions, allowing the breaker to protect electrical distribution equipment against overload and short-circuit conditions.
The 1SDA104317R1 features a fixed three-pole configuration with rear flat horizontal terminals and a rated uninterrupted current of 1250 A. It provides an ultimate and service short-circuit breaking capacity of 50 kA at 900 V AC, making it suitable for demanding industrial, infrastructure and energy distribution installations.
Air circuit breakers protect high-current electrical distribution systems by interrupting fault currents and disconnecting circuits when operating conditions exceed configured protection thresholds. The ABB Emax 2 platform combines high breaking performance with electronic protection technology for dependable operation in demanding power networks.
The Ekip Dip LSI trip unit fitted to the 1SDA104317R1 provides adjustable overload, short-time and instantaneous short-circuit protection. Combined with the E2.2S/E9 breaker's 50 kA breaking capacity at 900 V AC, the unit provides robust protection for installations requiring high operating voltage and substantial fault-current withstand capability.
Tick the specs you need, then view products that match.
| Voltage | 900 V AC | |
|---|---|---|
| Device Type | ACB | |
| Series | SACE Emax 2 / Emax 2 E9 | |
| Order code | 1SDA104317R1 | |
| Product type | Air circuit breaker | |
| Frame | E2.2S/E9 | |
| Rated current (In) | 1250 A | |
| Rated uninterrupted current (Iu) | 1250 A | |
| Rated voltage (Ur) | 900 V | |
| Rated operational voltage | 900 V AC | |
| Rated insulation voltage (Ui) | 1000 V AC | |
| Rated impulse withstand voltage (Uimp) | 12 kV | |
| Rated ultimate short-circuit breaking capacity (Icu) | 50 kA at 800 V AC / 50 kA at 900 V AC | |
| Rated service short-circuit breaking capacity (Ics) | 50 kA at 800 V AC / 50 kA at 900 V AC | |
| Rated short-time withstand current (Icw) | 50 kA for 1 s / 50 kA for 3 s | |
| Number of poles | 3P | |
| Installation | Fixed | |
| Terminal connection | Rear flat horizontal | |
| Trip unit | Ekip Dip LSI | |
| Release type | Electronic | |
| Protection functions | LSI – Long-time, Short-time and Instantaneous | |
| Overload release adjustment range | 500–1250 A | |
| Short-time short-circuit adjustment range | 750–12500 A | |
| Instantaneous short-circuit adjustment range | 1875–18750 A | |
| Short-circuit performance level | S | |
| Current type | AC | |
| Power loss | 83 W | |
| Protection rating | IP30 | |
| Mechanical durability | 25,000 cycles | |
| Electrical durability | 2,000 cycles at 900 V | |
| Dimensions (H × W × D) | 371 × 276 × 270 mm | |
| Weight | 41 kg | |
| Standard | IEC | |
| EAN | 8015644063979 | |
| Product group | Emax2 Air Circuit Breaker |
The ABB 1SDA104317R1 is an Emax 2 E2.2S/E9 air circuit breaker used for switching and protecting high-current AC power distribution systems against overload and short-circuit conditions.
The circuit breaker has a rated uninterrupted current Iu of 1250 A.
The E2.2S/E9 circuit breaker has a rated operational voltage of 900 V AC and a rated insulation voltage of 1000 V AC.
The circuit breaker provides a rated ultimate short-circuit breaking capacity Icu of 50 kA at 900 V AC, with an Ics service breaking capacity of 50 kA at the same voltage.
The breaker is fitted with an ABB Ekip Dip LSI electronic trip unit, providing long-time overload, short-time short-circuit and instantaneous short-circuit protection.
ABB SACE Emax 2 air circuit breakers combine high-performance switching and short-circuit interruption with advanced electronic protection, providing dependable circuit protection for industrial, infrastructure and energy distribution systems.
We use cookies