Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA083662R1 is a 200 A three-pole Tmax T4V-HA 250 moulded case circuit breaker for 800 V AC systems with adjustable TMA thermomagnetic protection, fixed mounting, front terminals and 25 kA Icu at 800 V AC.
£1,277.98
The ABB T4V-HA 250 TMA 200-2000 3P F F 800V AC, order code 1SDA083662R1, is a three-pole moulded case circuit breaker (MCCB) from the ABB Tmax range, engineered for high-voltage AC distribution applications. Built on the T4V-HA 250 A frame, it combines thermomagnetic protection with an operating voltage of 800 V AC.
This circuit breaker has a 200 A rated current and incorporates an ABB TMA thermomagnetic release. Its thermal protection is adjustable from 0.7–1 × In, corresponding to 140–200 A, while the magnetic protection is adjustable from 5–10 × In, corresponding to 1000–2000 A.
The 1SDA083662R1 is supplied as a fixed three-pole circuit breaker with front terminals. At its rated operational voltage of 800 V AC, it provides an ultimate short-circuit breaking capacity of 25 kA and a service short-circuit breaking capacity of 12 kA, making it suitable for demanding industrial and specialised power-distribution installations.
The ABB TMA release combines adjustable thermal overload protection with adjustable magnetic short-circuit protection. On this 200 A model, the thermal setting can be adjusted from 140–200 A, while the magnetic setting can be configured from 1000–2000 A, allowing the breaker protection to be coordinated with the requirements of the protected circuit.
The T4V-HA platform is engineered for operation at 800 V AC, where suitable insulation and fault-interruption performance are essential. With 25 kA Icu, 12 kA Ics, fixed mounting and front terminals, the 1SDA083662R1 provides a practical solution for demanding high-voltage AC distribution equipment.
Tick the specs you need, then view products that match.
| Voltage | 800 V AC | |
|---|---|---|
| Device Type | MCCB | |
| Series | Tmax T4V-HA | |
| Product family | T-Max XT 250 Range | |
| ABB order code | 1SDA083662R1 | |
| Product type | Moulded case circuit breaker (MCCB) | |
| Frame | T4V-HA | |
| Frame rating | 250 A | |
| Rated current | 200 A | |
| Rated uninterrupted current | 200 A | |
| Trip unit | TMA thermomagnetic | |
| Thermal protection setting | 0.7–1 × In | |
| Thermal adjustment range | 140–200 A | |
| Magnetic protection setting | 5–10 × In | |
| Magnetic adjustment range | 1000–2000 A | |
| Number of poles | 3 | |
| Installation | Fixed | |
| Terminal configuration | Front terminals | |
| Rated operational voltage | 800 V AC | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 8 kV | |
| Ultimate short-circuit breaking capacity (Icu) at 800 V AC | 25 kA | |
| Service short-circuit breaking capacity (Ics) at 800 V AC | 12 kA | |
| Rated frequency | 50/60 Hz | |
| Mechanical endurance | 20,000 cycles | |
| Electrical endurance at 800 V | 2,000 cycles | |
| Dimensions (H × W × D) | 205 × 140 × 103.5 mm | |
| Weight | 2.5 kg | |
| Standards | IEC / CCC |
The ABB 1SDA083662R1 is a T4V-HA 250 three-pole moulded case circuit breaker rated at 200 A and 800 V AC, with a TMA thermomagnetic release, fixed mounting and front terminals.
The circuit breaker has a rated current of 200 A and a rated operational voltage of 800 V AC.
The thermal protection is adjustable from 140–200 A, or 0.7–1 × In, while the magnetic short-circuit protection is adjustable from 1000–2000 A, or 5–10 × In.
At 800 V AC, the circuit breaker has an ultimate short-circuit breaking capacity (Icu) of 25 kA and a service short-circuit breaking capacity (Ics) of 12 kA.
The 1SDA083662R1 is supplied as a fixed three-pole circuit breaker with front terminals for integration into compatible switchboards, distribution panels and specialised 800 V AC electrical assemblies.
ABB Tmax moulded case circuit breakers provide dependable switching and circuit protection for demanding industrial, commercial and specialised power-distribution applications, including systems operating at elevated AC voltages.
We use cookies