Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131F9932 VLT HVAC Drive FC-102, a 45 kW / 60 HP three phase 380-480 V AC variable frequency drive with IP20 chassis enclosure and RFI Class A1/B filter for HVAC fan, pump and building services motor control applications.
£2,960.10
The Danfoss 131F9932 is a 45 kW / 60 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame C3, IP20 / chassis unit, built for mounting inside a control panel or enclosure.
This configuration has RFI class A1/B (C1), no brake chopper, and no local control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 45 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 45 kW | |
|---|---|---|
| Phase | Three Phase | |
| IP Rating | IP20 | |
| EMC Filter | Commercial | |
| Series | VLT HVAC Drive FC-102 | |
| Part number | 131F9932 | |
| Product type | AC variable frequency drive | |
| Rated output power | 45 kW / 60 HP | |
| Continuous current | 90 A normal overload | |
| Input voltage | 380–480 V AC | |
| Input phases | 3-phase | |
| Output phases | 3-phase | |
| Supply frequency | 50 / 60 Hz | |
| Protection rating | IP20 / chassis | |
| Frame size | C3 | |
| RFI filter | Class A1/B / C1 | |
| Brake chopper | Not included | |
| Local control panel | Not included | |
| PCB coating | Not coated | |
| Mains option | No mains option | |
| Dimensions (H × W × D) | approx. 550 × 308 × 333 mm | |
| Weight | approx. 35.3 kg |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Continuous output current is 90 A normal overload; intermittent current is listed in the specifications. Always size on the motor nameplate current at your supply voltage.
Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.
FC-102P45KT4E20H1XXXXXXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 45 kW / 60 HP | P45K |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP20 / chassis | E20 |
| RFI filter Position 16–17 | RFI class A1/B (C1) | H1 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | No local control panel | X |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies