137X0852 Danfoss 55kW Three Phase iC7-Automation Variable Speed Drive

137X0852 Danfoss 55kW Three Phase iC7-Automation Variable Speed Drive

Danfoss 137X0852 iC7-Automation rectifier input: 55 kW, 3×380-500 V AC supply, IP21 / TYPE 1.

SKU: 137X0852Alt SKU: IC7-60FA3N05-106AE21F3+AGCX+BAMT+BDBA+BEF1+BF20+DAAUMPN: 137X0852
Price
List Price £9,854.00 ex VAT
Your Price (ex VAT) Save 25%
£7,390.50 25% OFF
You save £2,463.50 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,390.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,390.50

Danfoss 137X0852 at a glance

The Danfoss 137X0852 is an iC7-Automation rectifier input rated 55 kW for 3x380-500 V AC supplies. It is an IP21 / TYPE 1 unit.

The iC7-Automation range is used for industrial automation, machine control and motor-driven process applications. This page lists the ratings that define this exact rectifier input; full electrical data, dimensions and installation requirements are in the manufacturer's documentation.

Key ratings

  • Rated output power: 55 kW
  • Supply: 3x380-500 V AC
  • Protection rating: IP21 / TYPE 1
  • Frame size: FK07
  • Typical motor power (light overload): 55KW(400V)/75HP(460V)
  • Continuous current, high overload (IH): 90/81A
  • Functional safety: STO, not upgradable
  • Control panel: Control Panel 2.8 OPX20
  • Communication: Modbus TCP OS7MT
  • On-board I/O: 4xDI,2xDI/O,2xAI,1xAO,2xRO
  • Brake chopper: No brake chopper
  • PCB coating: Coated PCB
  • Maximum output frequency: 590Hz

Choosing the right size

Size a drive on the motor nameplate current at your actual supply voltage, not on kW alone. Constant-torque loads (conveyors, mixers, hoists, compressors) need the heavy-duty / high-overload rating; variable-torque loads (centrifugal fans and pumps) can use the light-duty rating. If you are unsure, send us the motor nameplate details and the application and we will confirm the right Danfoss drive.

Technical Specifications

Tick the specs you need, then view products that match.

Power 55 kW
Current 106 A
Phase Three Phase
IP Rating IP21
EMC Filter Industrial
Product type 3~
Power rating 55 kW/75 hp
Mains voltage 380-500 V AC
Net weight 37.5 Kilogram
EAN 5715253794761
Ambient temp HO (1/10 min) 45°C/113°F
Ambient temp HO2 (1/5 min) 45°C/113°F
Ambient temp LO (1/10 min) 45°C/113°F
Ambient temp. normal overload 45°C/113°F
Cable entry and EMC plate Standard plate
Communication interface, X0 Ethernet port, no protocol
Communication interface, X1/X2 Modbus TCP OS7MT
Continous current IH (1/10min) 106/96A
Continous current IH (1/5min) 90/81A
Continous current IL (1/10min) 106/96A
Control panel Control Panel 2.8 OPX20
Current rating 106 A
Customer specific application None
Customer-specific label None
Customization file package ID No customization
DC terminals None
Efficiency class-Relative loss IE2 - 1.54%
EMC category C3 category
Enclosure rating IP21 / TYPE 1
Extra environmental protection Coated boards
Frame designation FK07
Functional safety STO, not upgradable
Gross weight 43.35 Kilogram
Heat sink access panel None
Help Counter 1
High speed enabled No
Humidity protection device None
Input curent HO2 (1/5 min) 85/74A
Input current HO (1/10 min) 103/90A
Input current in Normal Overlo 103/90A
Input current LO (1/10 min) 103/90A
Input frequency 50/60Hz
Input Voltage 3x380-500V
Integrated brake chopper None
Integrated common-mode filter None
Interface board MicroSD card reader and RTC
Language package Global
Main unit Depth 327 MM / 12.9 IN
Main unit Height 770 MM / 30.3 IN
Main unit Width 239 MM / 9.4 IN
Mains input device None
Maximum Power Loss LO [W] 1204
Modelcode01 IC7-60FA3N05-106AE21F3
Modelcode02 +AGCX
Modelcode03 +BAMT+BDBA
Modelcode04 +BEF1+BF20
Modelcode05 +DAAU
Option slot A None
Option slot B None, not upgradable
Option slot C None
Option slot D None
Option Slot E None
Output frequency 0-590Hz
Overload current IH (1/10min) 159/144A
Overload current IH (1/5min) 135/122A
Overload current IL (1/10min) 117/106A
Product category Frequency converter,air-cooled
Product group iC7-60
Product series iC7-Automation
Product software ID Latest released version
Product specific marine cert. None
Protection rating IP21/UL Type 1
Short circuit current rating 100kA
Standard I/O 4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO
Technical documentation Installation guide
Touch protection None
Typecode Part 1 7FC-AUFA3N05-106AE21F3
Typecode Part 2 -000157152
Typical motor power PH (150%) 55KW(400V)/75HP(460V)
Typical motor power PH2 (150%) 45KW(400V)/60HP(460V)
Typical motor power PL (110%) 55KW(400V)/75HP(460V)

Frequently asked questions

What motor power is the 137X0852 rated for?

55 kW.

What supply voltage does it need?

3x380-500 V AC.

Does it need to go inside a control panel?

Not necessarily. It is rated IP21 / TYPE 1, which allows mounting outside a panel where the environment suits that rating.

What is the full Danfoss type code?

IC7-60FA3N05-106AE21F3+AGCX+BAMT+BDBA+BEF1+BF20+DAAU.