137X0616 Danfoss 250kW Three Phase iC7-Automation Variable Speed Drive

137X0616 Danfoss 250kW Three Phase iC7-Automation Variable Speed Drive

137X0616 Danfoss 250kW Three Phase iC7-Automation Variable Speed Drive. Danfoss 137X0616 variable speed drive (frequency converter). Power rating: 250 kW/350 hp. Supply: 380-500 V AC.

SKU: 137X0616Alt SKU: IC7-60FA3N05-480AE20F3+AGCX+BAMT+BDBA+BEF1+BF20+CAD0+DAAUMPN: 137X0616
Price
List Price £24,046.00 ex VAT
Your Price (ex VAT) Save 25%
£18,034.50 25% OFF
You save £6,011.50 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £18,034.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£18,034.50

Why Choose the 137X0616?

The Danfoss 137X0616 (model code IC7-60FA3N05-480AE20F3+AGCX+BAMT+BDBA+BEF1+BF20+CAD0+DAAU) is a Variable speed drive (frequency converter) intended for panel installation where accurate motor control, repeatable commissioning, and reliable like-for-like replacement are required.

Configured with Power: 250 kW/350 hp, Current: 480 A, Supply: 380-500 V AC to support correct selection and like-for-like replacements.

Key Benefits

  • Variable speed drive (frequency converter) for correct application matching
  • Configured with Power: 250 kW/350 hp, Current: 480 A, Supply: 380-500 V AC.
  • Suitable for panel installations where reliable commissioning is required.
  • SKU and model code shown for procurement and like for like replacements.

Technical Specifications

Tick the specs you need, then view products that match.

Power 250 kW
Current 480 A
Phase Three Phase
IP Rating IP20
EMC Filter Industrial
Product type 3~
Power rating 250 kW/350 hp
Mains voltage 380-500 V AC
Net weight 108.83 Kilogram
EAN 5715253792347
Ambient temp HO (1/10 min) 45°C/113°F
Ambient temp HO2 (1/5 min) 45°C/113°F
Ambient temp LO (1/10 min) 40°C/104°F
Ambient temp. high overload 45°C/113°F
Ambient temp. normal overload 40°C/104°F
Cable entry and EMC plate Standard plate
Communication interface, X0 Ethernet port, no protocol
Communication interface, X1/X2 Modbus TCP OS7MT
Continous current IH (1/10min) 385/364A
Continous current IH (1/5min) 302/302A
Continous current IL (1/10min) 480/456A
Control panel Control Panel 2.8 OPX20
Current rating 480 A
Customer specific application None
Customer-specific label None
Customization file package ID No customization
DC terminals None
Efficiency class-Relative loss IE2 - 1.83%
EMC category C3 category
Enclosure rating IP20 / OPEN TYPE
Extra environmental protection Coated boards
Frame designation FA10
Functional safety STO, not upgradable
Gross weight 124.94 Kilogram
Heat sink access panel None
Help Counter 1
High speed enabled No
Humidity protection device None
Input curent HO2 (1/5 min) 291/291A
Input current HO (1/10 min) 371/350A
Input current in High Overload 371/350A
Input current in Normal Overlo 462/439A
Input current LO (1/10 min) 462/439A
Input frequency 50/60Hz
Input Voltage 3x380-500V
Integrated brake chopper None
Integrated common-mode filter None
Interface board MicroSD card reader and RTC
Language package Global
Main unit Depth 370 MM / 14.6 IN
Main unit Height 1122 MM / 44.2 IN
Main unit Width 350 MM / 13.8 IN
Mains input device None
Maximum Power Loss LO [W] 5123
Modelcode01 IC7-60FA3N05-480AE20F3
Modelcode02 +AGCX
Modelcode03 +BAMT+BDBA
Modelcode04 +BEF1+BF20+CAD0
Modelcode05 +DAAU
Option slot A Digital 230 V AC Input OC7D0
Option slot B None, not upgradable
Option slot C None
Option slot D None
Option Slot E None
Output frequency 0-590Hz
Overload current IH (1/10min) 578/546A
Overload current IH (1/5min) 453/453A
Overload current IL (1/10min) 528/502A
Plant from Orderline F605
Product category Frequency converter,air-cooled
Product group iC7-60
Product series iC7-Automation
Product software ID Latest released version
Product specific marine cert. None
Protection rating IP20/Open Type
Short circuit current rating 100kA
Standard I/O 4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO
Technical documentation Installation guide
Touch protection None
Typecode Part 1 7FC-AUFA3N05-480AE20F3
Typecode Part 2 -000156115
Typical motor power PH (150%) 200KW(400V)/300HP(460V)
Typical motor power PH2 (150%) 160KW(400V)/250HP(460V)
Typical motor power PL (110%) 250KW(400V)/350HP(460V)

Frequently Asked Questions

What supply does Danfoss 137X0616 require?
It is specified for 380-500 V AC. Match this to your incoming mains.
What is the rated power for 137X0616?
The listed power rating is 250 kW/350 hp. Confirm sizing against your motor and duty cycle.
Where is 137X0616 typically installed?
In control panels or cabinets. Follow Danfoss installation guidance for clearances, earthing, and protective devices.
What does IP20 mean for 137X0616?
IP20 indicates protection against finger contact and solid objects over 12.5 mm. Install in a suitable enclosure to meet your site requirements.
Can 137X0616 be used for pump and fan applications?
Yes, when correctly sized and commissioned, frequency converters are commonly used to control pumps and fans for smoother starts and improved process control.
What should I check before ordering a like for like replacement for 137X0616?
Confirm supply voltage, power rating, current rating, enclosure class, and required EMC filtering or communications options match the existing installation.