137N4947 Danfoss 710kW Three Phase iC7-Automation Variable Speed Drive

137N4947 Danfoss 710kW Three Phase iC7-Automation Variable Speed Drive

Danfoss 137N4947 iC7-Automation rectifier input: 710 kW, 3×380-500 V AC supply, IP21 / TYPE 1.

SKU: 137N4947Alt SKU: IC7-60FA3N05-1260E21F3+AGCX+AHHX+AJFX+BAMT+BDBA+BEF1+BF20+DAAUMPN: 137N4947
Price
List Price £96,071.00 ex VAT
Your Price (ex VAT) Save 25%
£72,053.25 25% OFF
You save £24,017.75 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £72,053.25
Trade pricing is personalised to your account

Manufacturer Lead Time

£72,053.25

Danfoss 137N4947 at a glance

The Danfoss 137N4947 is an iC7-Automation rectifier input rated 710 kW for 3x380-500 V AC supplies. It is an IP21 / TYPE 1 unit.

The iC7-Automation range is used for industrial automation, machine control and motor-driven process applications. This page lists the ratings that define this exact rectifier input; full electrical data, dimensions and installation requirements are in the manufacturer's documentation.

Key ratings

  • Rated output power: 710 kW
  • Supply: 3x380-500 V AC
  • Protection rating: IP21 / TYPE 1
  • Frame size: FK12
  • Typical motor power (light overload): 710KW(400V)/1000HP(460V)
  • Continuous current, high overload (IH): 1000/896A
  • Functional safety: STO, not upgradable
  • Control panel: Control Panel 2.8 OPX20
  • Communication: Modbus TCP OS7MT
  • On-board I/O: 4xDI,2xDI/O,2xAI,1xAO,2xRO
  • Brake chopper: No brake chopper
  • PCB coating: Coated PCB
  • Maximum output frequency: 590Hz

Choosing the right size

Size a drive on the motor nameplate current at your actual supply voltage, not on kW alone. Constant-torque loads (conveyors, mixers, hoists, compressors) need the heavy-duty / high-overload rating; variable-torque loads (centrifugal fans and pumps) can use the light-duty rating. If you are unsure, send us the motor nameplate details and the application and we will confirm the right Danfoss drive.

Technical Specifications

Tick the specs you need, then view products that match.

Power 710 kW
Current 1260 A
Phase Three Phase
IP Rating IP21
EMC Filter Industrial
Product type 3~
Power rating 710 kW/1000 hp
Mains voltage 380-500 V AC
Net weight 297.01 Kilogram
EAN 5715253628370
Ambient temp HO (1/10 min) 45°C/113°F
Ambient temp HO2 (1/5 min) 45°C/113°F
Ambient temp LO (1/10 min) 40°C/104°F
Ambient temp. high overload 45°C/113°F
Ambient temp. normal overload 40°C/104°F
Cable entry and EMC plate Standard plate
Communication interface, X0 Ethernet port, no protocol
Communication interface, X1/X2 Modbus TCP OS7MT
Continous current IH (1/10min) 1100/1028A
Continous current IH (1/5min) 1000/896A
Continous current IL (1/10min) 1260/1150A
Control panel Control Panel 2.8 OPX20
Current rating 1260 A
Customer specific application None
Customer-specific label None
Customization file package ID No customization
DC terminals None
Efficiency class-Relative loss IE2 - 1.91%
EMC category C3 category
Enclosure rating IP21 / TYPE 1
Extra environmental protection Coated boards
Frame designation FK12
Functional safety STO, not upgradable
Gross weight 350.12 Kilogram
Heat sink access panel None
Help Counter 1
High speed enabled No
Humidity protection device Space heater
Input curent HO2 (1/5 min) 963/863A
Input current HO (1/10 min) 1059/990A
Input current in High Overload 1059/990A
Input current in Normal Overlo 1200/1107A
Input current LO (1/10 min) 1200/1107A
Input frequency 50/60Hz
Input Voltage 3x380-500V
Integrated brake chopper None
Integrated common-mode filter None
Interface board MicroSD card reader and RTC
Language package Global
Main unit Depth 510 MM / 20.1 IN
Main unit Height 2043 MM / 80.4 IN
Main unit Width 698 MM / 27.5 IN
Mains input device AC fuses
Maximum Power Loss LO [W] 15402
Modelcode01 IC7-60FA3N05-1260E21F3
Modelcode02 +AGCX+AHHX+AJFX
Modelcode03 +BAMT+BDBA
Modelcode04 +BEF1+BF20
Modelcode05 +DAAU
Option slot A None
Option slot B None, not upgradable
Option slot C None
Option slot D None
Option Slot E None
Output frequency 0-590Hz
Overload current IH (1/10min) 1650/1542A
Overload current IH (1/5min) 1500/1344A
Overload current IL (1/10min) 1386/1265A
Product category Frequency converter,air-cooled
Product group iC7-60
Product series iC7-Automation
Product software ID Latest released version
Product specific marine cert. None
Protection rating IP21/UL Type 1
Short circuit current rating 100kA
Standard I/O 4xDI, 2xDI/O, 2xAI, 1xAO, 2xRO
Technical documentation Installation guide
Touch protection None
Typecode Part 1 7FC-AUFA3N05-1260E21F3
Typecode Part 2 -000134588
Typical motor power PH (150%) 630KW(400V)/900HP(460V)
Typical motor power PH2 (150%) 560KW(400V)/750HP(460V)
Typical motor power PL (110%) 710KW(400V)/1000HP(460V)

Frequently asked questions

What motor power is the 137N4947 rated for?

710 kW.

What supply voltage does it need?

3x380-500 V AC.

Does it need to go inside a control panel?

Not necessarily. It is rated IP21 / TYPE 1, which allows mounting outside a panel where the environment suits that rating.

What is the full Danfoss type code?

IC7-60FA3N05-1260E21F3+AGCX+AHHX+AJFX+BAMT+BDBA+BEF1+BF20+DAAU.