137N4545 Danfoss 500kW iC7-Automation Inverter module

137N4545 Danfoss 500kW iC7-Automation Inverter module

Danfoss 137N4545 iC7-Automation inverter module: 500 kW, 400/460/500 V AC supply, IP00 / Open type.

SKU: 137N4545Alt SKU: IC7-60SAIN05-880AE00F4+AE10+AKFX+BAMT+BDC1+BEXX+BF20+BGK1+BH15+BK15+CAM0+CBT0+DAAU+EGIN+EHENMPN: 137N4545
Price
List Price £37,754.00 ex VAT
Your Price (ex VAT) Save 25%
£28,315.50 25% OFF
You save £9,438.50 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £28,315.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£28,315.50

Danfoss 137N4545 at a glance

The Danfoss 137N4545 is an iC7-Automation inverter module rated 500 kW for 400/460/500 V AC supplies. It is an IP00 / Open type unit.

The iC7-Automation range is used for industrial automation, machine control and motor-driven process applications. This page lists the ratings that define this exact inverter module; full electrical data, dimensions and installation requirements are in the manufacturer's documentation.

Key ratings

  • Rated output power: 500 kW
  • Supply: 400/460/500 V AC
  • Protection rating: IP00 / Open type
  • Frame size: IR11
  • Typical motor power (light overload): 500KW(400V)/700HP(460V)
  • Continuous current, light overload (IL): 880A(400VAC)/820A(460VAC)
  • Continuous current, high overload (IH): 731A(400VAC)/681A(460VAC)
  • Nominal AC current: 899A(400VAC)/838A(460VAC)
  • Functional safety: None, not upgradable
  • Cooling: Air Cooling
  • Control panel: Control Panel 2.8 OPX20
  • Communication: Modbus TCP OS7MT
  • On-board I/O: 6xDI,2xDO,2xAI,1xAO,thermister input,2xNO/NC,1xNO relays
  • DC-bus voltage: 465-740VDC
  • Brake chopper: No brake chopper
  • PCB coating: Coated PCB
  • Maximum output frequency: 599Hz

Choosing the right size

Size a drive on the motor nameplate current at your actual supply voltage, not on kW alone. Constant-torque loads (conveyors, mixers, hoists, compressors) need the heavy-duty / high-overload rating; variable-torque loads (centrifugal fans and pumps) can use the light-duty rating. If you are unsure, send us the motor nameplate details and the application and we will confirm the right Danfoss drive.

Technical Specifications

Tick the specs you need, then view products that match.

Power 500 kW
Current 880 A
IP Rating IP00
EMC Filter None
Product type Inverter module, INU
Power rating 500 kW/650 HP
Mains voltage 380-500 V AC
Net weight 102 Kilogram
EAN 5715253624143
AC voltage 3X0-400/460/500VAC
check if complete OK
Communication interface, X0 Ethernet port, no protocol
Communication interface, X1/X2 Modbus TCP OS7MT
Continous current IH (1/5min) 731A(400VAC)/681A(460VAC)
Continous current IL (1/5min) 880A(400VAC)/820A(460VAC)
Control panel Control Panel 2.8 OPX20
Control panel cable length 1.5 m (5 ft)
Control panel mounting type Flush mount
Control unit cable length 1.5 m (5 ft), Fiber
Cooling circuit connector type Not relevant
Cooling circuit hose length Not relevant
Cooling type Air Cooled
Current rating 880 A
Customer specific application None
Customer-specific label None
Customization file package ID No customization
DC Bus current 1015A(540VDC)
DC Bus voltage 465-740VDC
DC fuses and devices DC bus fuses
DC power 548kW(540VDC)
Documentation language English
EMC category C4 category
Enclosure rating IP00 / OPEN TYPE
Extra environmental protection Coated boards
Frame designation IR11
Functional safety None, not upgradable
Gross weight 132 Kilogram
Help Counter 1
High speed enabled No
Integration unit Standard, no filter
Language package Global
Main unit Depth 553MM/21.8IN
Main unit Height 1530MM/60.2IN
Main unit Width 235MM/9.3IN
Mains input device None
Marine construction None
Modelcode01 IC7-60SAIN05-880AE00F4
Modelcode02 +AE10+AKFX
Modelcode03 +BAMT+BDC1+BEXX+BF20
Modelcode04 +BGK1+BH15+BK15+CAM0+CBT0
Modelcode06 +DAAU
Modelcode08 +EGIN+EHEN
Nominal AC current 899A(400VAC)/838A(460VAC)
Option slot A Encoder/Resolver Option OC7M0
Option slot B Temperature Measurement OC7T0
Option slot C None, without mounting plate
Option slot D None, without mounting plate
Option slot E None, without mounting plate
Option slot F None, without mounting plate
Option slot G None, without mounting plate
Option slot H None, without mounting plate
Option slot I None, without mounting plate
Option slot J None, without mounting plate
Output frequency 0-590Hz
Overload current IH (1/5min) 1097A(400VAC)/1022A(460VAC)
Overload current IL (1/5min) 968A(400VAC)/902A(460VAC)
Product category System module, air-cooled
Product Category -DrivesSymbol System module, air-cooled
Product group iC7-60
Product series iC7-Automation
Product software ID Latest released version
Product specific marine cert. None
Product Type - DrivesSymbol Inverter module
Protection rating IP00/Open Type
Salescode part 1 IC7-60SAIN05-880AE00F4
Salescode part 2 +AE10+AKFX
Salescode part 3 +BAMT+BDC1+BEXX+BF20
Salescode part 4 +BGK1+BH15+BK15+CAM0+CBT0
Salescode part 5 +DAAU
Salescode part 6 +EGIN+EHEN
Shipping package Cardboard box package
Short circuit current rating 100kA
Standard I/O I/O and Relay Option OC7C1
StarCoupler board cable length None
Start current Imax (3sec) 1243A
Storage temperature -40...70°C/-40...158°F
Technical documentation Installation guide
Typecode Part 1 7SM-AUSAIN05-880AE00F4
Typecode Part 2 -000134146
Typical motor power PH2 (150%) 400kW(400VAC)/550Hp(460VAC)
Typical motor power PL (110%) 500kW(400VAC)/700Hp(460VAC)

Frequently asked questions

What motor power is the 137N4545 rated for?

500 kW.

What supply voltage does it need?

400/460/500 V AC.

Does it need to go inside a control panel?

Yes. It is rated IP00 / Open type, so it is designed to be mounted inside an enclosure or control panel.

What is the full Danfoss type code?

IC7-60SAIN05-880AE00F4+AE10+AKFX+BAMT+BDC1+BEXX+BF20+BGK1+BH15+BK15+CAM0+CBT0+DAAU+EGIN+EHEN.