136F9062 Danfoss VLT Automation Drive FC- 302 5.5 KW / 7.5 HP, 380 - 500 VAC, IP20

136F9062 Danfoss VLT Automation Drive FC- 302 5.5 KW / 7.5 HP, 380 – 500 VAC, IP20

136F9062 Danfoss VLT Automation Drive FC- 302 5.5 KW / 7.5 HP, 380 – 500 VAC, IP20. Danfoss 136F9062 variable speed drive (frequency converter). Power rating: (P5K5) 5.5 KW / 7.5 HP. Supply: 380 – 500 VAC.

SKU: 136F9062Alt SKU: FC-302P5K5T5E20H2XGXXXXSXXXXALB2CXXXXDXMPN: 136F9062
Price
List Price £2,060.00 ex VAT
Your Price (ex VAT) Save 25%
£1,545.00 25% OFF
You save £515.00 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,545.00
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,545.00

Why Choose the 136F9062?

The Danfoss 136F9062 (model code FC-302P5K5T5E20H2XGXXXXSXXXXALB2CXXXXDX) is a Variable speed drive (frequency converter) intended for panel installation where accurate motor control, repeatable commissioning, and reliable like-for-like replacement are required.

Configured with Power: (P5K5) 5.5 KW / 7.5 HP, Current: 11, Supply: 380 - 500 VAC, Phase: Three phase, Enclosure: (E20) IP20 / Chassis, EMC/RFI: RFI Filter to support correct selection and like-for-like replacements.

Key Benefits

  • Variable speed drive (frequency converter) for correct application matching
  • Configured with Power: (P5K5) 5.5 KW / 7.5 HP, Current: 11, Supply: 380 - 500 VAC, Phase: Three phase, Enclosure: (E20) IP20 / Chassis, EMC/RFI: RFI Filter.
  • Suitable for panel installations where reliable commissioning is required.
  • SKU and model code shown for procurement and like for like replacements.

Technical Specifications

Tick the specs you need, then view products that match.

Power 5.5 kW
Voltage 500 V
Phase Three Phase
IP Rating IP20
Series 302
Power Rating (P5K5) 5.5 KW / 7.5 HP
Mains Voltage 380 - 500 VAC
Enclosure (E20) IP20 / Chassis
RFI Filter RFI Filter
Height [mm] 268,0
Width w/ no C options [mm] 130,0
Depth [mm] 205,0
Net weight 6.29 Kilogram
EAN 5710108554965
A Option PROFINET MCA 120
Adaptation A Standard Cable Entries
Adaptation B No adaptation
ATEX Marking 1 ATEX: II (2) G [Ex eb Gb] [Ex
ATEX Marking 2 db Gb] / II (2) D [Ex tb Db]
B Option MCB-112 PTC Therm. Card
Brake - Safe Stop No brake chopper
C Option Software No software option
C0 Option MCO No C0 option
C1 Option No C1 option
Coating PCB Not coated PCB
Continuous Current (HO) [A] 11
D Option No D option
Depth with Option A/B [mm] 220,0
Frame Size A3
Gross weight 7.296 Kilogram
Intermittent Current (HO) [A] 17.6
LCP Graphical Loc. Cont. Panel
Mains Option No Mains Option
Modelcode01 FC-302P5K5T5E20H2XGX
Modelcode02 XXXSXXXXALB2CXXXXDX
Plant from Orderline B901
Power 160% (HO) [KW] 5.5
Power Loss HO [W] 187
Product Group VLT® AutomationDrive FC-
Software Language Pack Standard Language Pack
Software Release Latest release std. SW.
Typecode Part 1 FC-302P5K5T5E20H2XGX
Typecode Part 2 XXXSXXXXALB2CXXXXDX
Width w/ two C options [mm] 190,0

Frequently Asked Questions

What supply does Danfoss 136F9062 require?
It is specified for 380 - 500 VAC. Match this to your incoming mains.
What is the rated power for 136F9062?
The listed power rating is (P5K5) 5.5 KW / 7.5 HP. Confirm sizing against your motor and duty cycle.
What enclosure class is it?
It is listed as (E20) IP20 / Chassis and is intended for installation in a suitable cabinet/enclosure as required.
Does it include an EMC/RFI filter?
The configuration is shown as RFI Filter. Choose a filtered variant or external filtering if your site requires it.
Where is 136F9062 typically installed?
In control panels or cabinets. Follow Danfoss installation guidance for clearances, earthing, and protective devices.
What does IP20 mean for 136F9062?
IP20 indicates protection against finger contact and solid objects over 12.5 mm. Install in a suitable enclosure to meet your site requirements.