135X5147 Danfoss VLT Automation Drive FC- 302 160 KW / 250 HP, 380 - 500 VAC, IP54

135X5147 Danfoss VLT Automation Drive FC- 302 160 KW / 250 HP, 380 – 500 VAC, IP54

135X5147 Danfoss VLT Automation Drive FC- 302 160 KW / 250 HP, 380 – 500 VAC, IP54. Danfoss 135X5147 variable speed drive (frequency converter). Power rating: (N160) 160 KW / 250 HP. Supply: 380 – 500 VAC.

SKU: 135X5147Alt SKU: FC-302N160T5E54H2XGCXXXSXXXXALBXCXXXXDXMPN: 135X5147
Price
List Price £20,481.00 ex VAT
Your Price (ex VAT) Save 25%
£15,360.75 25% OFF
You save £5,120.25 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £15,360.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£15,360.75

Why Choose the 135X5147?

The Danfoss 135X5147 (model code FC-302N160T5E54H2XGCXXXSXXXXALBXCXXXXDX) is a Variable speed drive (frequency converter) intended for panel installation where accurate motor control, repeatable commissioning, and reliable like-for-like replacement are required.

Configured with Power: (N160) 160 KW / 250 HP, Current: 361, Supply: 380 - 500 VAC, Phase: Three phase, Enclosure: (E54) IP54 / Type 12, EMC/RFI: RFI Filter to support correct selection and like-for-like replacements.

Key Benefits

  • Variable speed drive (frequency converter) for correct application matching
  • Configured with Power: (N160) 160 KW / 250 HP, Current: 361, Supply: 380 - 500 VAC, Phase: Three phase, Enclosure: (E54) IP54 / Type 12, EMC/RFI: RFI Filter.
  • Suitable for panel installations where reliable commissioning is required.
  • SKU and model code shown for procurement and like for like replacements.

Technical Specifications

Tick the specs you need, then view products that match.

Power 160 kW
Voltage 500 V
Phase Three Phase
IP Rating IP54
Series 302
Power Rating (N160) 160 KW / 250 HP
Mains Voltage 380 - 500 VAC
Enclosure (E54) IP54 / Type 12
RFI Filter RFI Filter
Height [mm] 1060,0
Width w/ no C options [mm] 420,0
Depth [mm] 378,0
Net weight 106 Kilogram
EAN 5710108414375
A Option PROFINET MCA 120
Adaptation A Standard Cable Entries
Adaptation B No adaptation
B Option No B Option
Brake - Safe Stop No brake chopper
C Option Software No software option
C0 Option MCO No C0 option
C1 Option No C1 option
Coating PCB Coated PCB
Continuous Current (HO) [A] 302
Continuous Current (NO) [A] 361
D Option No D option
Depth with Option A/B [mm] 378,0
Frame Size D2H
Gross weight 121 Kilogram
Intermittent Current (HO) [A] 453
Intermittent Current (NO) [A] 397
LCP Graphical Loc. Cont. Panel
Mains Option No Mains Option
Modelcode01 FC-302N160T5E54H2XGC
Modelcode02 XXXSXXXXALBXCXXXXDX
Power 110% (NO) [KW] 200
Power 150% (HO) [KW] 160
Product Group VLT® AutomationDrive FC-
Software Language Pack Standard Language Pack
Software Release Latest release std. SW.
Typecode Part 1 FC-302N160T5E54H2XGC
Typecode Part 2 XXXSXXXXALBXCXXXXDX

Frequently Asked Questions

What supply does Danfoss 135X5147 require?
It is specified for 380 - 500 VAC. Match this to your incoming mains.
What is the rated power for 135X5147?
The listed power rating is (N160) 160 KW / 250 HP. Confirm sizing against your motor and duty cycle.
What enclosure class is it?
It is listed as (E54) IP54 / Type 12 and is intended for installation in a suitable cabinet/enclosure as required.
Does it include an EMC/RFI filter?
The configuration is shown as RFI Filter. Choose a filtered variant or external filtering if your site requires it.
Where is 135X5147 typically installed?
In control panels or cabinets. Follow Danfoss installation guidance for clearances, earthing, and protective devices.
What does IP20 mean for 135X5147?
IP20 indicates protection against finger contact and solid objects over 12.5 mm. Install in a suitable enclosure to meet your site requirements.