Danfoss 135X3313 VLT HVAC Drive FC 102 variable speed drive, 18.5 kW / 25 HP, three-phase 525-600 V AC, IP66 / NEMA 4X enclosure, designed for HVAC motor control applications.
£1,954.70
The Danfoss 135X3313 is an 18.5 kW VLT HVAC Drive FC 102 for 3 × 525–600 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B1, IP66 / UL Type 4X unit, built for wall mounting in wet, dusty or wash-down locations.
This configuration has no RFI filter, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Tick the specs you need, then view products that match.
| Power | 18.5 kW | |
|---|---|---|
| Voltage | 600 V | |
| Phase | Three Phase | |
| IP Rating | IP66 | |
| EMC Filter | None | |
| Series | VLT® HVAC Drive FC 102 | |
| Part Number | 135X3313 | |
| Model Code | FC-102P18KT6E66HXXGXXXXSXXXXAXBXCXXXXDX | |
| Product type | Variable speed drive / frequency converter | |
| Rated output power | 18.5 kW | |
| Horsepower rating | 25 HP | |
| Input voltage | 525-600 V AC | |
| Input phases | Three-phase | |
| Frequency | 50 / 60 Hz | |
| Protection rating | IP66 / NEMA 4X | |
| RFI filter | No RFI filter | |
| Brake chopper | No brake chopper | |
| Control panel | Graphical Local Control Panel | |
| PCB type | Not coated PCB | |
| Mains option | No mains option | |
| A option | No A option | |
| B option | No B option | |
| C1 option | No C1 option | |
| D option | No D option | |
| Frame size | B1 |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP66 / UL Type 4X enclosure is designed for direct mounting.
FC-102P18KT6E66HXXGXXXXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 18.5 kW | P18K |
| Mains voltage Position 11–12 | 3 × 525–600 V AC | T6 |
| Enclosure Position 13–15 | IP66 / UL Type 4X | E66 |
| RFI filter Position 16–17 | No RFI filter | HX |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies