135U7396 Danfoss VLT HVAC Drive 400 kW/550HP 380-480VAC IP54

135U7396 Danfoss VLT HVAC Drive 400 kW/550HP 380-480VAC IP54

Danfoss 135U7396 VLT HVAC Drive FC 102, a 400 kW three-phase AC variable frequency drive designed for large HVAC motor control applications including pumps, fans, compressors and refrigeration systems.

SKU: 135U7396Alt SKU: FC-102N400T4E5MH2XGC7XXSXXXXAXBKCXXXXDXMPN: 135U7396
Price
List Price £37,183.00 ex VAT
Your Price (ex VAT) Save 45%
£20,450.65 45% OFF
You save £16,732.35 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £20,450.65
Trade pricing is personalised to your account

Manufacturer Lead Time

£20,450.65

Danfoss 135U7396 at a glance

The Danfoss 135U7396 is a 400 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame E1H, IP54 / UL Type 12 with mains shield unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A2 (C3), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP54 / UL Type 12 with mains shield — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Smaller355 kWDanfoss 136F7795IP54 / UL Type 12 with mains shield · frame E1HView drive →
This drive400 kWDanfoss 135U7396IP54 / UL Type 12 with mains shield · frame E1H

Same 400 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 400 kW
Current 678 A
Voltage 480 V
Phase Three Phase
IP Rating IP54
EMC Filter Industrial
Series VLT HVAC Drive FC 102
Part Number FC-102N400T4E5MH2XGC7XXSXXXXAXBKCXXXXDX
Product type AC variable frequency drive
Rated output power 400 kW
Motor horsepower 550 HP
Current rating 678 A
Input voltage 380-480 V AC
Input phases 3-phase
Output phases 3-phase
Frequency 50 / 60 Hz
Protection rating IP54 / Type 12 with main shield
RFI filter Class A2 (C3)
Brake chopper Not included
Control panel Graphical Local Control Panel
PCB coating Coated PCB
B option MCB-101 general purpose I/O
Fuse option Included
Frame size E1H
Dimensions (H × W × D) approx. 2000 × 600 × 510 mm
Net weight approx. 211 kg
EAN 5710108336646

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Can this drive be wall mounted without a panel?

Yes. The IP54 / UL Type 12 with mains shield enclosure is designed for direct mounting.

Type code decoded

FC-102N400T4E5MH2XGC7XXSXXXXAXBKCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
400 kWN400
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP54 / UL Type 12 with mains shieldE5M
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
Fuses7
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
MCB 101 general-purpose I/OBK
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX