Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 135U7396 VLT HVAC Drive FC 102, a 400 kW three-phase AC variable frequency drive designed for large HVAC motor control applications including pumps, fans, compressors and refrigeration systems.
£20,450.65
The Danfoss 135U7396 is a 400 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame E1H, IP54 / UL Type 12 with mains shield unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A2 (C3), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 400 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 400 kW | |
|---|---|---|
| Current | 678 A | |
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP54 | |
| EMC Filter | Industrial | |
| Series | VLT HVAC Drive FC 102 | |
| Part Number | FC-102N400T4E5MH2XGC7XXSXXXXAXBKCXXXXDX | |
| Product type | AC variable frequency drive | |
| Rated output power | 400 kW | |
| Motor horsepower | 550 HP | |
| Current rating | 678 A | |
| Input voltage | 380-480 V AC | |
| Input phases | 3-phase | |
| Output phases | 3-phase | |
| Frequency | 50 / 60 Hz | |
| Protection rating | IP54 / Type 12 with main shield | |
| RFI filter | Class A2 (C3) | |
| Brake chopper | Not included | |
| Control panel | Graphical Local Control Panel | |
| PCB coating | Coated PCB | |
| B option | MCB-101 general purpose I/O | |
| Fuse option | Included | |
| Frame size | E1H | |
| Dimensions (H × W × D) | approx. 2000 × 600 × 510 mm | |
| Net weight | approx. 211 kg | |
| EAN | 5710108336646 |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP54 / UL Type 12 with mains shield enclosure is designed for direct mounting.
FC-102N400T4E5MH2XGC7XXSXXXXAXBKCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 400 kW | N400 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP54 / UL Type 12 with mains shield | E5M |
| RFI filter Position 16–17 | RFI class A2 (C3) | H2 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Conformal-coated PCBs | C |
| Mains option Position 21 | Fuses | 7 |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | MCB 101 general-purpose I/O | BK |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.