134X8915 Danfoss VLT HVAC Drive 630 kW/900HP 380-480VAC IP54

134X8915 Danfoss VLT HVAC Drive 630 kW/900HP 380-480VAC IP54

Danfoss 134X8915 VLT HVAC Drive FC-102, a 630 kW / 900 HP three phase AC variable frequency drive with IP54 / Type 12 enclosure, Safe Stop, PROFINET MCA 120 communication, coated PCB and fuse option for large HVAC applications.

SKU: 134X8915Alt SKU: FC-102P630T4E54H2TGC7XXSXXXXALBXCXXXXDXMPN: 134X8915
Price
List Price £93,651.00 ex VAT
Your Price (ex VAT) Save 45%
£51,508.05 45% OFF
You save £42,142.95 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £51,508.05
Trade pricing is personalised to your account

Manufacturer Lead Time

£51,508.05

Danfoss 134X8915 at a glance

The Danfoss 134X8915 is a 630 kW / 900 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame F1, IP54 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A2 (C3), safe Stop, no brake chopper, a graphical LCP 102 control panel, and a PROFINET MCA 120 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP54 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 630 kW rating, other enclosures

This driveIP54Danfoss 134X8915IP54 / UL Type 12
EnclosureIP21Danfoss 131G7331IP21 / UL Type 1View drive →

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 630 kW
Voltage 480 V
Phase Three Phase
IP Rating IP54
EMC Filter Industrial
Series VLT HVAC Drive FC-102
SKU 134X8915
Product type AC variable frequency drive
Rated output power 630 kW / 900 HP
Input voltage 380–480 V AC
Input phases 3-phase
Output phases 3-phase
Protection rating IP54 / Type 12
RFI filter Class A2 (C3)
Safety function Safe Stop
Control panel Graphical Local Control Panel
Communication option PROFINET MCA 120
B option No B option
PCB coating Coated PCB
Mains option Fuse
Frame size F1
Software Latest release standard software

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a PROFINET MCA 120 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Can this drive be wall mounted without a panel?

Yes. The IP54 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102P630T4E54H2TGC7XXSXXXXALBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
630 kW / 900 HPP630
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP54 / UL Type 12E54
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
Safe Stop, no brake chopperT
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
Fuses7
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
PROFINET MCA 120AL
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX