134U7664 Danfoss VLT HVAC Drive 11 kW/15HP 380-480VAC IP20

134U7664 Danfoss VLT HVAC Drive 11 kW/15HP 380-480VAC IP20

Danfoss 134U7664 VLT HVAC Drive FC 102, an 11 kW three-phase variable frequency drive with Safe Stop, IP20 chassis enclosure, PROFIBUS DP MCA 101 and MCB-112 PTC thermistor card for HVAC motor control applications.

SKU: 134U7664Alt SKU: FC-102P11KT4E20H1TGXXXXSXXXXA0B2CXXXXDXMPN: 134U7664
Price
List Price £2,430.00 ex VAT
Your Price (ex VAT) Save 45%
£1,336.50 45% OFF
You save £1,093.50 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,336.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,336.50

Danfoss 134U7664 at a glance

The Danfoss 134U7664 is an 11 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B3, IP20 / chassis unit, built for mounting inside a control panel or enclosure.

This configuration has RFI class A1/B (C1), safe Stop, no brake chopper, a graphical LCP 102 control panel, and a PROFIBUS DP MCA 101 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP20 / chassis — built for mounting inside a control panel or enclosure.
  • EMC: RFI class A1/B (C1). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Smaller5.5 kWDanfoss 134F0281IP20 / chassis · frame A3View drive →
This drive11 kWDanfoss 134U7664IP20 / chassis · frame B3

Same 11 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 11 kW
Voltage 480 V
Phase Three Phase
IP Rating IP20
EMC Filter Commercial
Series VLT® HVAC Drive FC 102
Type code FC-102P11KT4E20H1TGXXXXSXXXXA0B2CXXXXDX
Product type Variable frequency drive
Rated output power 11 kW
Horsepower rating 15 HP
Input voltage 380–480 V AC
Input phases Three-phase
Output phases Three-phase
Application HVAC motor control
Protection rating IP20 / chassis
RFI filter Class A1/B (C1)
Brake / safety function Safe Stop
A option PROFIBUS DP MCA 101
B option MCB-112 PTC thermistor card
Local control panel Graphical LCP
PCB coating Not coated PCB
Mains option No mains option
Frame size B3
ATEX rating II (2) G [Ex eb Gb] [Exdb Gb] / II (2) D [Ex tb Db]

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a PROFIBUS DP MCA 101 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Does this drive need to go in an enclosure?

Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.

Type code decoded

FC-102P11KT4E20H1TGXXXXSXXXXA0B2CXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
11 kWP11K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP20 / chassisE20
RFI filter
Position 16–17
RFI class A1/B (C1)H1
Brake / Safe Stop
Position 18
Safe Stop, no brake chopperT
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
PROFIBUS DP MCA 101A0
B option (I/O)
Position 31–32
MCB 112 PTC thermistor cardB2
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX