134U3858 Danfoss VLT Automation Drive FC 300 110 KW / 150 HP, 380 - 500 VAC, IP20

134U3858 Danfoss VLT Automation Drive FC 300 110 KW / 150 HP, 380 – 500 VAC, IP20

134U3858 Danfoss VLT Automation Drive FC 300 110 KW / 150 HP, 380 – 500 VAC, IP20. Danfoss 134U3858 variable speed drive (frequency converter). Power rating: (N110) 110 KW / 150 HP. Supply: 380 – 500 VAC.

SKU: 134U3858Alt SKU: FC-302N110T5E20H4XGCXXXSXXXXAUBXCXXXXD0MPN: 134U3858
Price
List Price £14,577.00 ex VAT
Your Price (ex VAT) Save 25%
£10,932.75 25% OFF
You save £3,644.25 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,932.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,932.75

Why Choose the 134U3858?

The Danfoss 134U3858 (model code FC-302N110T5E20H4XGCXXXSXXXXAUBXCXXXXD0) is a Variable speed drive (frequency converter) intended for panel installation where accurate motor control, repeatable commissioning, and reliable like-for-like replacement are required.

Configured with Power: (N110) 110 KW / 150 HP, Current: 240, Supply: 380 - 500 VAC, Phase: Three phase, Enclosure: (E20) IP20 / Chassis, EMC/RFI: RFI class A1 (C2) to support correct selection and like-for-like replacements.

Key Benefits

  • Variable speed drive (frequency converter) for correct application matching
  • Configured with Power: (N110) 110 KW / 150 HP, Current: 240, Supply: 380 - 500 VAC, Phase: Three phase, Enclosure: (E20) IP20 / Chassis, EMC/RFI: RFI class A1 (C2).
  • Suitable for panel installations where reliable commissioning is required.
  • SKU and model code shown for procurement and like for like replacements.

Technical Specifications

Tick the specs you need, then view products that match.

Power 110 kW
Voltage 500 V
Phase Three Phase
IP Rating IP20
EMC Filter Commercial
Series 302
Power Rating (N110) 110 KW / 150 HP
Mains Voltage 380 - 500 VAC
Enclosure (E20) IP20 / Chassis
RFI Filter RFI class A1 (C2)
Height [mm] 909,0
Width w/ no C options [mm] 250,0
Depth [mm] 375,0
Net weight 78 Kilogram
EAN 5710107998814
A Option PROFIBUS Converter MCA114
Adaptation A Standard Cable Entries
Adaptation B No adaptation
B Option No B Option
Brake - Safe Stop No brake chopper
C Option Software No software option
C0 Option MCO No C0 option
C1 Option No C1 option
Coating PCB Coated PCB
Continuous Current (HO) [A] 190
Continuous Current (NO) [A] 240
D Option MCB-107 24V DC backup
Depth with Option A/B [mm] 375,0
Frame Size D3H
Gross weight 78 Kilogram
Height w/ Regen/Loadshare [mm] 1004,0
Intermittent Current (HO) [A] 285
Intermittent Current (NO) [A] 264
LCP Graphical Loc. Cont. Panel
Mains Option No Mains Option
Modelcode01 FC-302N110T5E20H4XGC
Modelcode02 XXXSXXXXAUBXCXXXXD0
Power 110% (NO) [KW] 132
Power 150% (HO) [KW] 110
Power Loss HO [W] 2051
Power Loss NO [W] 2724
Product Group VLT® AutomationDrive FC-
Software Language Pack Standard Language Pack
Software Release Latest release std. SW.
Typecode Part 1 FC-302N110T5E20H4XGC
Typecode Part 2 XXXSXXXXAUBXCXXXXD0

Frequently Asked Questions

What supply does Danfoss 134U3858 require?
It is specified for 380 - 500 VAC. Match this to your incoming mains.
What is the rated power for 134U3858?
The listed power rating is (N110) 110 KW / 150 HP. Confirm sizing against your motor and duty cycle.
What enclosure class is it?
It is listed as (E20) IP20 / Chassis and is intended for installation in a suitable cabinet/enclosure as required.
Does it include an EMC/RFI filter?
The configuration is shown as RFI class A1 (C2). Choose a filtered variant or external filtering if your site requires it.
Where is 134U3858 typically installed?
In control panels or cabinets. Follow Danfoss installation guidance for clearances, earthing, and protective devices.
What does IP20 mean for 134U3858?
IP20 indicates protection against finger contact and solid objects over 12.5 mm. Install in a suitable enclosure to meet your site requirements.