134L9594 Danfoss VLT HVAC Drive 15 kW/20HP 525-690VAC IP21

134L9594 Danfoss VLT HVAC Drive 15 kW/20HP 525-690VAC IP21

Danfoss 134L9594 VLT HVAC Drive FC 102 variable frequency drive featuring 15 kW output power, three-phase 525–690 V AC supply, IP21 / Type 1 enclosure, RFI Class A1 / C2 filtering, brake chopper, Safe Stop and graphical local control panel for HVAC motor control applications.

SKU: 134L9594Alt SKU: FC-102P15KT7E21H4UGCXXXSXXXXAXBXCXXXXDXMPN: 134L9594
Price
List Price £3,485.00 ex VAT
Your Price (ex VAT) Save 45%
£1,916.75 45% OFF
You save £1,568.25 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,916.75
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,916.75

Danfoss 134L9594 at a glance

The Danfoss 134L9594 is a 15 kW (20 HP) VLT HVAC Drive FC 102 for 3 × 525–690 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B2, IP21 / UL Type 1 unit, suitable for mounting in clean, dry indoor plant rooms.

This configuration has RFI class A1 (C2), brake chopper + Safe Stop, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP21 / UL Type 1 — suitable for mounting in clean, dry indoor plant rooms.
  • EMC: RFI class A1 (C2). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

This drive15 kWDanfoss 134L9594IP21 / UL Type 1 · frame B2
Larger75 kWDanfoss 134N0936IP21 / UL Type 1 · frame C2View drive →

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 15 kW
Voltage 690 V
Phase Three Phase
IP Rating IP21
EMC Filter Commercial
Series VLT® HVAC Drive FC 102
Part Number 134L9594
Product type AC variable frequency drive
Rated output power 15 kW (20 HP)
Specific ratings 11 kW at 525–550 V, 15 HP at 575 V, 15 kW at 690 V
Output current 18 A
Input voltage 525–690 V AC
Input phases 3-phase
Output phases 3-phase
Protection rating IP21 / Type 1
EMC Filter RFI Class A1 / C2
Brake function Brake chopper + Safe Stop
Control panel Graphical local control panel
Mains option No mains option
PCB protection Coated PCB
Frame size B2
Mounting type Cabinet / panel mounting

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Can this drive be wall mounted without a panel?

Yes. The IP21 / UL Type 1 enclosure is designed for direct mounting.

Type code decoded

FC-102P15KT7E21H4UGCXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
15 kW (20 HP)P15K
Mains voltage
Position 11–12
3 × 525–690 V ACT7
Enclosure
Position 13–15
IP21 / UL Type 1E21
RFI filter
Position 16–17
RFI class A1 (C2)H4
Brake / Safe Stop
Position 18
Brake chopper + Safe StopU
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX