Danfoss 134H1101 VLT HVAC Drive FC-102 variable frequency drive, 160 kW three phase 380-480 V AC IP54 / Type 12 drive with RFI Class A2 (C3) filter, graphical LCP and coated PCB 3C3 ruggedised construction for high-power HVAC motor control applications.
£8,809.35
The Danfoss 134H1101 is a 160 kW (250 HP) VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame D1H, IP54 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A2 (C3), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same 160 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 160 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP54 | |
| EMC Filter | Industrial | |
| Series | VLT HVAC Drive FC-102 | |
| Part Number | 134H1101 | |
| Model Code | FC-102N160T4E54H2XGRXXXSXXXXAXBXCXXXXDX | |
| Product type | AC variable frequency drive | |
| Rated output power | 160 kW (250 HP) | |
| Input voltage | 380–480 V AC | |
| Input phases | 3-phase | |
| Frequency | 50 / 60 Hz | |
| Protection rating | IP54 / Type 12 | |
| RFI filter | Class A2 (C3) | |
| Brake chopper | No brake chopper | |
| Local control panel | Graphical LCP | |
| PCB coating | Coated PCB 3C3 + ruggedised | |
| Mains option | No mains option | |
| A option | No A option | |
| B option | No B option | |
| Frame size | D1H | |
| Gross weight | approx. 80 kg | |
| Net weight | approx. 75 kg | |
| EAN | 5710107661121 |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP54 / UL Type 12 enclosure is designed for direct mounting.
FC-102N160T4E54H2XGRXXXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 160 kW (250 HP) | N160 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP54 / UL Type 12 | E54 |
| RFI filter Position 16–17 | RFI class A2 (C3) | H2 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Ruggedised, coated PCBs | R |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.