Danfoss 134G9289 VLT HVAC Drive FC 102, rated at 315 kW / 450 HP for 525-690 V AC three-phase HVAC motor control applications, supplied in an IP54 / Type 12 enclosure with main shield, RFI Class A2/C3 filter, fuse, MCB 109 I/O with RTC backup and coated PCB.
The Danfoss 134G9289 is a 315 kW VLT HVAC Drive FC 102 for 3 × 525–690 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP54 / UL Type 12 with mains shield unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A2 (C3), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Tick the specs you need, then view products that match.
| Power | 315 kW | |
|---|---|---|
| Voltage | 690 V | |
| Phase | Three Phase | |
| IP Rating | IP54 | |
| EMC Filter | Industrial | |
| Drive series | VLT HVAC Drive FC 102 | |
| Product type | Variable frequency drive / HVAC inverter drive | |
| Power rating | 315 kW / 450 HP | |
| Supply voltage | 525–690 V AC | |
| Input phase | Three-phase | |
| Enclosure rating | IP54 / Type 12 | |
| Main shield | Included | |
| RFI filter | Class A2 / C3 | |
| Brake chopper | No | |
| Mains option | Fuse | |
| A option | No A option | |
| B option | MCB 109 I/O with RTC backup | |
| PCB coating | Coated PCB | |
| Application | HVAC motor speed control |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP54 / UL Type 12 with mains shield enclosure is designed for direct mounting.
FC-102P315T7E5MH2XGC7XXSXXXXAXB0CXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 315 kW | P315 |
| Mains voltage Position 11–12 | 3 × 525–690 V AC | T7 |
| Enclosure Position 13–15 | IP54 / UL Type 12 with mains shield | E5M |
| RFI filter Position 16–17 | RFI class A2 (C3) | H2 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Conformal-coated PCBs | C |
| Mains option Position 21 | Fuses | 7 |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | MCB 109 analogue I/O with real-time-clock back-up | B0 |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies