134F9456 Danfoss VLT HVAC Drive 250 kW/350HP 380-480VAC IP54

134F9456 Danfoss VLT HVAC Drive 250 kW/350HP 380-480VAC IP54

Danfoss 134F9456 VLT HVAC Drive FC 102 variable frequency drive featuring 250 kW output power, three-phase 380–480 V AC supply, IP54 / Type 12 enclosure with main shield, RFI Class A1 (C2) filtering, graphical local control panel, coated PCB, fuse option and no brake chopper for HVAC motor control applications.

SKU: 134F9456Alt SKU: FC-102N250T4E5MH4XGC7XXSXXXXAXBXCXXXXDXMPN: 134F9456
Price
List Price £25,942.00 ex VAT
Your Price (ex VAT) Save 45%
£14,268.10 45% OFF
You save £11,673.90 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £14,268.10
Trade pricing is personalised to your account

Manufacturer Lead Time

£14,268.10

Danfoss 134F9456 at a glance

The Danfoss 134F9456 is a 250 kW (350 HP) VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame D2H, IP54 / UL Type 12 with mains shield unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1 (C2), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP54 / UL Type 12 with mains shield — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1 (C2). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 250 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 250 kW
Voltage 480 V
Phase Three Phase
IP Rating IP54
EMC Filter Commercial
Series VLT® HVAC Drive FC 102
Part Number 134F9456
Rated output power 250 kW (350 HP)
Input voltage 380–480 V AC
Input phases 3-phase
Output phases 3-phase
Protection rating IP54 / Type 12 with main shield
EMC Filter RFI Class A1 (C2)
Brake function No brake chopper
Control panel Graphical local control panel
Option Fuse
PCB protection Coated PCB
Software Latest release standard software
Frame size D2H
A option No A option
B option No B option
C1 option No C1 option
D option No D option

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Can this drive be wall mounted without a panel?

Yes. The IP54 / UL Type 12 with mains shield enclosure is designed for direct mounting.

Type code decoded

FC-102N250T4E5MH4XGC7XXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
250 kW (350 HP)N250
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP54 / UL Type 12 with mains shieldE5M
RFI filter
Position 16–17
RFI class A1 (C2)H4
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
Fuses7
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX