134F6989 Danfoss VLT FC-102 HVAC Drive 1.5 kW / 2.0 HP, 380 - 480 VAC, IP55

134F6989 Danfoss VLT FC-102 HVAC Drive 1.5 kW / 2.0 HP, 380 – 480 VAC, IP55

Danfoss 134F6989 VLT HVAC Drive FC-102, a 1.5 kW / 2.0 HP three phase HVAC frequency converter for 380-480 V AC motor control applications with IP55 enclosure, RFI Class A1/B filter and PROFIBUS DP MCA 101 option.

SKU: 134F6989Alt SKU: FC-102P1K5T4Z55H1XGXXXXSXXXXA0BXCXXXXDXMPN: 134F6989
Price
List Price £1,110.00 ex VAT
Your Price (ex VAT) Save 45%
£610.50 45% OFF
You save £499.50 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £610.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£610.50

Danfoss 134F6989 at a glance

The Danfoss 134F6989 is a 1.5 kW / 2.0 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A4, IP55 / UL Type 12, A4 frame unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1/B (C1), no brake chopper, a graphical LCP 102 control panel, and a PROFIBUS DP MCA 101 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Continuous output current: 4.1 A / 3.4 A. Size the drive on the motor nameplate current at your actual supply voltage.
  • Intermittent (overload) current: 4.51 A / 3.74 A — the normal-overload rating that suits variable-torque fan and pump loads.
  • Enclosure: IP55 / UL Type 12, A4 frame — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1/B (C1). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 1.5 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 1.5 kW
Voltage 480 V
Phase Three Phase
IP Rating IP55
EMC Filter Commercial
Series VLT HVAC Drive FC-102
Model / SKU 134F6989
Type code FC-102P1K5T4Z55H1XGXXXXSXXXXA0BXCXXXXDX
Product type HVAC frequency converter / variable speed drive
Rated output power 1.5 kW / 2.0 HP
Mains voltage 380-480 V AC
Input phases Three phase
Enclosure IP55 / Type 12 A4 frame
RFI filter RFI Class A1/B (C1)
Brake chopper No brake chopper
Local control panel Graphical LCP
PCB coating Not coated PCB
Mains option No mains option
Adaptation A Standard cable entries
Adaptation B No adaptation
Software release Latest release standard software
Software language pack Standard language pack
A option PROFIBUS DP MCA 101
B option No B option
C0 option No C0 option
C1 option No C1 option
C option software No software option
D option No D option
Frame size A4
kVA rating 2.84 kVA
Power loss 62 W
Continuous current 4.1 A / 3.4 A
Intermittent current 4.51 A / 3.74 A
Dimensions (H x W x D) approx. 391 x 200 x 177 mm
Volume approx. 47.293 litres
Net weight approx. 7.89 kg
Gross weight approx. 8.626 kg
EAN 5710107472383

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a PROFIBUS DP MCA 101 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

What output current does it deliver at 400 V and at 480 V?

Continuous output current is 4.1 A / 3.4 A; intermittent current is 4.51 A / 3.74 A. Always size on the motor nameplate current at your supply voltage.

Can this drive be wall mounted without a panel?

Yes. The IP55 / UL Type 12, A4 frame enclosure is designed for direct mounting.

Type code decoded

FC-102P1K5T4Z55H1XGXXXXSXXXXA0BXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
1.5 kW / 2.0 HPP1K5
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP55 / UL Type 12, A4 frameZ55
RFI filter
Position 16–17
RFI class A1/B (C1)H1
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
PROFIBUS DP MCA 101A0
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX