Danfoss 134F4022 VLT HVAC Drive FC-102, a 1.1 kW / 1.5 HP three phase 380-480 V AC variable frequency drive with IP20 chassis enclosure, RFI Class A1/B filter, graphical local control panel, no brake chopper, BACnet MCA 109 and MCB-109 I/O with RTC back-up for HVAC motor control applications.
£519.75
The Danfoss 134F4022 is a 1.1 kW / 1.5 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A2, IP20 / chassis unit, built for mounting inside a control panel or enclosure.
This configuration has RFI class A1/B (C1) with reduced motor cable length, no brake chopper, a graphical LCP 102 control panel, and a BACnet MCA 109 fieldbus card. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same 1.1 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 1.1 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP20 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC-102 | |
| Model / type code | FC-102P1K1T4E20H3XGXXXXSXXXXAJB0CXXXXDX | |
| Product code / SKU | 134F4022 | |
| Product type | HVAC variable frequency drive / frequency converter | |
| Rated output power | 1.1 kW / 1.5 HP | |
| Supply voltage | 380-480 V AC | |
| Input phases | Three phase | |
| Apparent power | 2.08 kVA | |
| Continuous current | 3 A | |
| Intermittent current | 3.3 A | |
| Power loss | 58 W | |
| Enclosure rating | IP20 / chassis | |
| RFI filter | Class A1/B (C1) | |
| Brake option | No brake chopper | |
| Control panel | Graphical local control panel | |
| PCB coating | Not coated PCB | |
| Mains option | No mains option | |
| Adaptation A | Standard cable entries | |
| A option | BACnet MCA 109 | |
| B option | MCB-109 I/O, RTC back-up | |
| C1 option | No C1 option | |
| D option | No D option | |
| Software release | Latest release standard software | |
| Frame size | A2 | |
| Dimensions (H × W × D) | approx. 268 × 90 × 205 mm | |
| Depth with option A/B | approx. 220 mm | |
| Net weight | approx. 4.66 kg | |
| Gross weight | approx. 5.506 kg | |
| Volume | 21.569 litres | |
| EAN | 5710107438495 |
The 134F4022 has the H3 filter: RFI class A1/B (C1) with a reduced motor cable length. The exact limit for this frame is in the Danfoss VLT HVAC Drive FC 102 Design Guide (see Technical Documents). If your screened cable run is longer, contact us and we will suggest an alternative.
This unit is fitted with a BACnet MCA 109 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.
Continuous output current is 3 A; intermittent current is 3.3 A. Always size on the motor nameplate current at your supply voltage.
Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.
FC-102P1K1T4E20H3XGXXXXSXXXXAJB0CXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 1.1 kW / 1.5 HP | P1K1 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP20 / chassis | E20 |
| RFI filter Position 16–17 | RFI class A1/B (C1) with reduced motor cable length | H3 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | BACnet MCA 109 | AJ |
| B option (I/O) Position 31–32 | MCB 109 analogue I/O with real-time-clock back-up | B0 |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies