Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 134F0427 VLT HVAC Drive FC-102, a 37 kW / 50 HP three phase 380-480 V AC variable frequency drive with IP55 / Type 12 enclosure, RFI Class A1/B filter, Safe Stop, graphical local control panel, no mains option and MCB-112 PTC thermistor card for HVAC motor control applications.
£2,896.30
The Danfoss 134F0427 is a 37 kW / 50 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame C1, IP55 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A1/B (C1) with reduced motor cable length, safe Stop, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 37 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 37 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP55 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC-102 | |
| Model / type code | FC-102P37KT4E55H3TGXXXXSXXXXAXB2CXXXXDX | |
| Product code / SKU | 134F0427 | |
| Product type | HVAC variable frequency drive / frequency converter | |
| Rated output power | 37 kW / 50 HP | |
| Supply voltage | 380-480 V AC | |
| Input phases | Three phase | |
| Apparent power | 50.6 kVA | |
| Continuous current | 73 A | |
| Intermittent current | 80.3 A | |
| Power loss | 739 W | |
| Enclosure rating | IP55 / Type 12 | |
| RFI filter | Class A1/B (C1) | |
| Brake / safety function | Safe Stop | |
| Control panel | Graphical local control panel | |
| PCB coating | Not coated PCB | |
| Mains option | No mains option | |
| A option | No A option | |
| B option | MCB-112 PTC thermistor card | |
| C1 option | No C1 option | |
| D option | No D option | |
| ATEX marking | II (2) G [Ex eb Gb] [Ex db Gb] / II (2) D [Ex tb Db] | |
| Frame size | C1 | |
| Dimensions (H × W × D) | approx. 685 × 308 × 311 mm | |
| Depth with option A/B | approx. 311 mm | |
| Net weight | approx. 39.94 kg | |
| Gross weight | approx. 42.94 kg | |
| Volume | 176.054 litres | |
| EAN | 5710107401345 |
The 134F0427 has the H3 filter: RFI class A1/B (C1) with a reduced motor cable length. The exact limit for this frame is in the Danfoss VLT HVAC Drive FC 102 Design Guide (see Technical Documents). If your screened cable run is longer, contact us and we will suggest an alternative.
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Continuous output current is 73 A; intermittent current is 80.3 A. Always size on the motor nameplate current at your supply voltage.
Yes. The IP55 / UL Type 12 enclosure is designed for direct mounting.
FC-102P37KT4E55H3TGXXXXSXXXXAXB2CXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 37 kW / 50 HP | P37K |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP55 / UL Type 12 | E55 |
| RFI filter Position 16–17 | RFI class A1/B (C1) with reduced motor cable length | H3 |
| Brake / Safe Stop Position 18 | Safe Stop, no brake chopper | T |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | MCB 112 PTC thermistor card | B2 |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |