131Z9225 Danfoss VLT FC-102 HVAC Drive 18.5 kW / 25 HP, 380 - 480 VAC, IP55

131Z9225 Danfoss VLT FC-102 HVAC Drive 18.5 kW / 25 HP, 380 – 480 VAC, IP55

Danfoss 131Z9225 VLT HVAC Drive FC-102 frequency converter, 18.5 kW / 25 HP, three phase 380-480 V AC, IP55 / Type 12 backplate, Safe Stop, RFI Class A1/B filter, graphical local control panel and mains disconnect, designed for HVAC motor control in ventilation, heating, refrigeration and air handling applications.

SKU: 131Z9225Alt SKU: FC-102P18KT4P55H1TGX1XXSXXXXAXBXCXXXXDXMPN: 131Z9225
Price
List Price £3,700.00 ex VAT
Your Price (ex VAT) Save 45%
£2,035.00 45% OFF
You save £1,665.00 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,035.00
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,035.00

Danfoss 131Z9225 at a glance

The Danfoss 131Z9225 is an 18.5 kW / 25 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B1, IP55 / UL Type 12 with backplate unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1/B (C1), safe Stop, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Continuous output current: 37.5 A / 34 A. Size the drive on the motor nameplate current at your actual supply voltage.
  • Intermittent (overload) current: 41.2 A / 37.4 A — the normal-overload rating that suits variable-torque fan and pump loads.
  • Enclosure: IP55 / UL Type 12 with backplate — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1/B (C1). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Same 18.5 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 18.5 kW
Voltage 480 V
Phase Three Phase
IP Rating IP55
EMC Filter Commercial
Series VLT® HVAC Drive FC-102
Product code 131Z9225
Model code FC-102P18KT4P55H1TGX1XXSXXXXAXBXCXXXXDX
Product type Frequency converter / variable speed drive
Application type HVAC drive
Rated power 18.5 kW / 25 HP
Input voltage 380-480 V AC
Input phases Three phase
Enclosure rating IP55 / Type 12 Backplate
RFI filter Class A1/B (C1)
Frame size B1
Control panel Graphical local control panel
Brake / safety function Safe Stop
PCB coating Not coated PCB
Mains option Mains disconnect
Adaptation A Standard cable entries
Adaptation B No adaptation
A option No A option
B option No B option
C0 option No C0 option
C1 option No C1 option
Software option No software option
D option No D option
Software release Latest release standard software
Language pack Standard language pack
Continuous current 37.5 A / 34 A
Intermittent current 41.2 A / 37.4 A
kVA rating 26 kVA
Power loss 465 W
Dimensions (H × W × D) 494 × 243 × 261 mm
Gross weight 26.37 kg
Net weight 22.75 kg
Volume 105.71 L
EAN 5710107389285

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

What output current does it deliver at 400 V and at 480 V?

Continuous output current is 37.5 A / 34 A; intermittent current is 41.2 A / 37.4 A. Always size on the motor nameplate current at your supply voltage.

Can this drive be wall mounted without a panel?

Yes. The IP55 / UL Type 12 with backplate enclosure is designed for direct mounting.

Type code decoded

FC-102P18KT4P55H1TGX1XXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
18.5 kW / 25 HPP18K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP55 / UL Type 12 with backplateP55
RFI filter
Position 16–17
RFI class A1/B (C1)H1
Brake / Safe Stop
Position 18
Safe Stop, no brake chopperT
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
Mains disconnect1
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX