Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131Z9224 VLT HVAC Drive FC-102 frequency converter, 7.5 kW / 10 HP, three phase 380-480 V AC, IP55 / Type 12 backplate, Safe Stop, RFI Class A1/B filter, graphical local control panel and mains disconnect, designed for HVAC motor control in ventilation, heating, refrigeration and air handling applications.
£1,202.85
The Danfoss 131Z9224 is a 7.5 kW / 10 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A5, IP55 / UL Type 12 with backplate unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A1/B (C1), safe Stop, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 7.5 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 7.5 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP55 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC-102 | |
| Product code | 131Z9224 | |
| Model code | FC-102P7K5T4P55H1TGX1XXSXXXXAXBXCXXXXDX | |
| Product type | Frequency converter / variable speed drive | |
| Application type | HVAC drive | |
| Rated power | 7.5 kW / 10 HP | |
| Input voltage | 380-480 V AC | |
| Input phases | Three phase | |
| Enclosure rating | IP55 / Type 12 Backplate | |
| RFI filter | Class A1/B (C1) | |
| Frame size | A5 | |
| Control panel | Graphical local control panel | |
| Brake / safety function | Safe Stop | |
| PCB coating | Not coated PCB | |
| Mains option | Mains disconnect | |
| Adaptation A | Standard cable entries | |
| Adaptation B | No adaptation | |
| A option | No A option | |
| B option | No B option | |
| C0 option | No C0 option | |
| C1 option | No C1 option | |
| Software option | No software option | |
| D option | No D option | |
| Software release | Latest release standard software | |
| Language pack | Standard language pack | |
| Continuous current | 16 A / 14.5 A | |
| Intermittent current | 17.6 A / 16 A | |
| kVA rating | 11.1 kVA | |
| Power loss | 255 W | |
| Dimensions (H × W × D) | 420 × 242 × 200 mm | |
| Gross weight | 14.126 kg | |
| Net weight | 13.51 kg | |
| Volume | 39.798 L | |
| EAN | 5710107389278 |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Continuous output current is 16 A / 14.5 A; intermittent current is 17.6 A / 16 A. Always size on the motor nameplate current at your supply voltage.
Yes. The IP55 / UL Type 12 with backplate enclosure is designed for direct mounting.
FC-102P7K5T4P55H1TGX1XXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 7.5 kW / 10 HP | P7K5 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP55 / UL Type 12 with backplate | P55 |
| RFI filter Position 16–17 | RFI class A1/B (C1) | H1 |
| Brake / Safe Stop Position 18 | Safe Stop, no brake chopper | T |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | Mains disconnect | 1 |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.