Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131Z2162 VLT HVAC Drive FC-102 frequency converter, model code FC-102P4K0T4E66H3XGXXOXSXXXXAXBXCXXXXDX, rated at 4 kW / 5 HP with three-phase 380-480 V AC supply, IP66 / NEMA 4X enclosure, RFI Class A1/B (C1) filter, graphical local control panel, not coated PCB and no brake chopper for HVAC motor control applications.
£850.30
The Danfoss 131Z2162 is a 4 kW / 5 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A5, IP66 / UL Type 4X unit, built for wall mounting in wet, dusty or wash-down locations.
This configuration has RFI class A1/B (C1) with reduced motor cable length, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 4 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 4 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP66 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC-102 | |
| SKU | 131Z2162 | |
| Model code | FC-102P4K0T4E66H3XGXXOXSXXXXAXBXCXXXXDX | |
| Product type | Frequency converter / variable speed drive | |
| Rated output power | 4 kW / 5 HP | |
| Rated output current | 10 A / 8.2 A | |
| Input voltage | 380-480 V AC | |
| Input phases | Three phase | |
| Application | HVAC motor control | |
| Enclosure rating | IP66 / NEMA 4X | |
| RFI filter | Class A1/B (C1) | |
| Brake chopper | No brake chopper | |
| Control panel | Graphical local control panel | |
| PCB coating | Not coated PCB | |
| Mains option | No mains option | |
| Frame size | A5 | |
| Adaptation A | Metric thread cable entry | |
| Adaptation B | No adaptation | |
| Option A | No A option | |
| Option B | No B option | |
| Option C0 | No C0 option | |
| Option C1 | No C1 option | |
| Option D | No D option | |
| Software release | Latest release standard software | |
| Software language pack | Standard language pack | |
| kVA rating | 6.93 kVA | |
| Power loss | 124 W | |
| Continuous current | 10 A / 8.2 A | |
| Intermittent current | 11 A / 9.02 A | |
| Dimensions (H × W × D) | approx. 420 × 242 × 200 mm |
The 131Z2162 has the H3 filter: RFI class A1/B (C1) with a reduced motor cable length. The exact limit for this frame is in the Danfoss VLT HVAC Drive FC 102 Design Guide (see Technical Documents). If your screened cable run is longer, contact us and we will suggest an alternative.
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Continuous output current is 10 A / 8.2 A; intermittent current is 11 A / 9.02 A. Always size on the motor nameplate current at your supply voltage.
Yes. The IP66 / UL Type 4X enclosure is designed for direct mounting.
FC-102P4K0T4E66H3XGXXOXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 4 kW / 5 HP | P4K0 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP66 / UL Type 4X | E66 |
| RFI filter Position 16–17 | RFI class A1/B (C1) with reduced motor cable length | H3 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Metric cable entries | O |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.