131X7669 Danfoss VLT HVAC Drive 400 kW/550HP 380-480VAC IP00

131X7669 Danfoss VLT HVAC Drive 400 kW/550HP 380-480VAC IP00

Danfoss 131X7669 VLT HVAC Drive FC 102, a 400 kW three-phase AC variable frequency drive designed for HVAC motor control applications including fans, pumps and compressors.

SKU: 131X7669Alt SKU: FC-102P400T4E00H2TGCXXXSXXXXAXBXCXXXXDXMPN: 131X7669
Price
List Price £40,161.00 ex VAT
Your Price (ex VAT) Save 45%
£22,088.55 45% OFF
You save £18,072.45 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £22,088.55
Trade pricing is personalised to your account

Manufacturer Lead Time

£22,088.55

Danfoss 131X7669 at a glance

The Danfoss 131X7669 is a 400 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP00 / chassis unit, built for mounting inside a control panel or enclosure.

This configuration has RFI class A2 (C3), safe Stop, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP00 / chassis — built for mounting inside a control panel or enclosure.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 400 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 400 kW
Voltage 480 V
Phase Three Phase
IP Rating IP00
EMC Filter Industrial
Series VLT® HVAC Drive FC 102
Part number 131X7669
Product type AC variable frequency drive
Rated output power 400 kW
Horsepower rating 550 HP
Input voltage 380–480 V AC
Input phases 3-phase
Output phases 3-phase
Frequency 50 / 60 Hz
Protection rating IP00 / chassis
EMC Filter RFI Class A2 / C3
Safety function Safe Stop
Control panel Graphical Local Control Panel
PCB coating Coated PCB
Brake chopper No brake chopper
Mains option No mains option

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Does this drive need to go in an enclosure?

Yes. IP00 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.

Type code decoded

FC-102P400T4E00H2TGCXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
400 kWP400
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP00 / chassisE00
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
Safe Stop, no brake chopperT
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX