Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131X2728 VLT HVAC Drive FC-102, a 75 kW / 100 HP three phase HVAC variable frequency drive with 380-480 V AC input, IP55 / Type 12 enclosure, RFI Class A1/B filter, numerical local control panel, PROFIBUS DP MCA 101 and MCB-107 24 V DC backup option.
£5,090.25
The Danfoss 131X2728 is a 75 kW / 100 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame C2, IP55 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A1/B (C1), no brake chopper, a numeric LCP 101 control panel, and a PROFIBUS DP MCA 101 fieldbus card. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same 75 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 75 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP55 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC-102 | |
| Model / Code | 131X2728 | |
| Type code | FC-102P75KT4E55H1XNCXXXSXXXXA0BXCXXXXD0 | |
| Product type | HVAC variable frequency drive | |
| Rated output power | 75 kW / 100 HP | |
| Continuous current | 147 A / 130 A | |
| Intermittent current | 162 A / 143 A | |
| Input voltage | 380-480 V AC | |
| Input phases | Three phase | |
| Enclosure rating | IP55 / Type 12 | |
| RFI filter | Class A1/B, C1 | |
| Brake chopper | No brake chopper | |
| Control panel | Numerical local control panel | |
| PCB coating | Coated PCB | |
| Mains option | No mains option | |
| Adaptation A | Standard cable entries | |
| Adaptation B | No adaptation | |
| A option | PROFIBUS DP MCA 101 | |
| B option | No B option | |
| C1 option | No C1 option | |
| D option | MCB-107 24 V DC backup | |
| Software | Latest release standard software | |
| Frame size | C2 | |
| Dimensions (H x W x D) | 780 x 370 x 332 mm | |
| Depth with option A/B | 332 mm | |
| kVA rating | 102 kVA | |
| Power loss | 1384 W | |
| EAN | 5710107045433 | |
| Net weight | approx. 57.37 kg | |
| Gross weight | approx. 60.71 kg | |
| Volume | approx. 232.653 litres |
This unit is fitted with a PROFIBUS DP MCA 101 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.
Continuous output current is 147 A / 130 A; intermittent current is 162 A / 143 A. Always size on the motor nameplate current at your supply voltage.
Yes. The IP55 / UL Type 12 enclosure is designed for direct mounting.
FC-102P75KT4E55H1XNCXXXSXXXXA0BXCXXXXD0
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 75 kW / 100 HP | P75K |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP55 / UL Type 12 | E55 |
| RFI filter Position 16–17 | RFI class A1/B (C1) | H1 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Numeric LCP 101 | N |
| PCB coating Position 20 | Conformal-coated PCBs | C |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | PROFIBUS DP MCA 101 | A0 |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | 24 V DC back-up (MCB 107) | D0 |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.