Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131X2638 VLT HVAC Drive FC-102, a 4.0 kW / 5.0 HP three phase HVAC variable frequency drive with 380-480 V AC input, IP55 / Type 12 backplate enclosure, graphical local control panel, RFI Class A1/B filter and BACnet MCA 109 option.
£831.05
The Danfoss 131X2638 is a 4.0 kW / 5.0 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A5, IP55 / UL Type 12 with backplate unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A1/B (C1) with reduced motor cable length, no brake chopper, a graphical LCP 102 control panel, and a BACnet MCA 109 fieldbus card. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 4 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 4 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP55 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC-102 | |
| Model / Code | 131X2638 | |
| Type code | FC-102P4K0T4P55H3XGXXOXSXXXXAJBXCXXXXDX | |
| Product type | HVAC variable frequency drive | |
| Rated output power | 4.0 kW / 5.0 HP | |
| Continuous current | 10 A / 8.2 A | |
| Intermittent current | 11 A / 9.02 A | |
| Input voltage | 380-480 V AC | |
| Input phases | Three phase | |
| Enclosure rating | IP55 / Type 12 | |
| Mounting / enclosure detail | Backplate | |
| RFI filter | Class A1/B, C1 | |
| Brake chopper | No brake chopper | |
| Control panel | Graphical local control panel | |
| PCB coating | Not coated PCB | |
| Mains option | No mains option | |
| Adaptation A | Metric thread cable entry | |
| Adaptation B | No adaptation | |
| A option | BACnet MCA 109 | |
| B option | No B option | |
| C1 option | No C1 option | |
| D option | No D option | |
| Software | Latest release standard software | |
| Frame size | A5 | |
| Dimensions (H x W x D) | 420 x 242 x 200 mm | |
| Depth with option A/B | 200 mm | |
| kVA rating | 6.93 kVA | |
| Power loss | 124 W | |
| EAN | 5710107044443 | |
| Net weight | approx. 12.12 kg | |
| Gross weight | approx. 12.736 kg | |
| Volume | approx. 39.798 litres |
The 131X2638 has the H3 filter: RFI class A1/B (C1) with a reduced motor cable length. The exact limit for this frame is in the Danfoss VLT HVAC Drive FC 102 Design Guide (see Technical Documents). If your screened cable run is longer, contact us and we will suggest an alternative.
This unit is fitted with a BACnet MCA 109 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.
Continuous output current is 10 A / 8.2 A; intermittent current is 11 A / 9.02 A. Always size on the motor nameplate current at your supply voltage.
Yes. The IP55 / UL Type 12 with backplate enclosure is designed for direct mounting.
FC-102P4K0T4P55H3XGXXOXSXXXXAJBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 4.0 kW / 5.0 HP | P4K0 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP55 / UL Type 12 with backplate | P55 |
| RFI filter Position 16–17 | RFI class A1/B (C1) with reduced motor cable length | H3 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Metric cable entries | O |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | BACnet MCA 109 | AJ |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies