Danfoss 131U0413 VLT AutomationDrive industrial AC variable frequency drive designed for advanced motor control, automation integration and energy-efficient industrial operation.
£22,068.75
The Danfoss 131U0413 is a 355 kW / 500 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP54 hybrid, low-harmonic drive unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has low-harmonic drive + RFI class A1, safe Stop, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same 355 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 355 kW | |
|---|---|---|
| Voltage | 480 V | |
| IP Rating | IP54 | |
| Series | VLT® AutomationDrive | |
| SKU | 131U0413 | |
| Product type | AC variable frequency drive | |
| Motor control | Induction and permanent magnet motors | |
| Control method | Advanced vector control | |
| Application | Industrial automation and process control | |
| Safety options | Available depending on configuration | |
| Mounting type | Panel / cabinet installation | |
| Protection rating | Configuration dependent | |
| Frequency | 50 / 60 Hz |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP54 hybrid, low-harmonic drive enclosure is designed for direct mounting.
FC-102P355T4E5HL4TGC3XXSXXXXAXBKCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 355 kW / 500 HP | P355 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP54 hybrid, low-harmonic drive | E5H |
| RFI filter Position 16–17 | Low-harmonic drive + RFI class A1 | L4 |
| Brake / Safe Stop Position 18 | Safe Stop, no brake chopper | T |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Conformal-coated PCBs | C |
| Mains option Position 21 | Mains disconnect + fuses | 3 |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | MCB 101 general-purpose I/O | BK |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies