131N9828 Danfoss VLT FC-102 HVAC Drive 4.0 kW / 5.5 HP, 380 - 480 VAC, IP55

131N9828 Danfoss VLT FC-102 HVAC Drive 4.0 kW / 5.5 HP, 380 – 480 VAC, IP55

Danfoss 131N9828 VLT HVAC Drive FC-102 frequency converter, a 4.0 kW three phase variable speed drive designed for HVAC motor control, energy efficiency and building automation applications.

SKU: 131N9828Alt SKU: FC-102P4K0T4Z55H3XGX1OXSXXXXAXBXCXXXXDXMPN: 131N9828
Price
List Price £1,510.00 ex VAT
Your Price (ex VAT) Save 45%
£830.50 45% OFF
You save £679.50 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £830.50
Trade pricing is personalised to your account

Manufacturer Lead Time

£830.50

Danfoss 131N9828 at a glance

The Danfoss 131N9828 is a 4.0 kW / 5.0 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A4, IP55 / UL Type 12, A4 frame unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1/B (C1) with reduced motor cable length, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Continuous output current: 8.2 A. Size the drive on the motor nameplate current at your actual supply voltage.
  • Intermittent (overload) current: 9.02 A — the normal-overload rating that suits variable-torque fan and pump loads.
  • Enclosure: IP55 / UL Type 12, A4 frame — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1/B (C1) is met only with a reduced screened motor cable length. Check the maximum length for this frame in the Danfoss FC 102 Design Guide (Technical Documents tab); for longer runs, ask us about an H2 (A2/C3) variant.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Smaller3 kWDanfoss 134F1871IP55 / UL Type 12, A4 frame · frame A4View drive →
This drive4 kWDanfoss 131N9828IP55 / UL Type 12, A4 frame · frame A4

Same 4 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 4 kW
Voltage 480 V
Phase Three Phase
IP Rating IP55
EMC Filter Commercial
Series VLT® HVAC Drive FC-102
SKU 131N9828
Product type Variable speed drive / frequency converter
Rated output power 4.0 kW / 5.0 HP
Continuous current 8.2 A
Intermittent current 9.02 A
Input voltage 380-480 V AC
Input phases Three phase
Frequency 50 / 60 Hz
Protection rating IP55 / Type 12
Frame size A4
RFI filter Class A1/B (C1)
Brake chopper No brake chopper
Control panel Graphical local control panel
PCB coating Not coated PCB
Mains option Mains disconnect
Dimensions (H × W × D) approx. 391 × 200 × 177 mm
Net weight approx. 8.16 kg
EAN 5702427908512

Frequently asked questions

What is the maximum motor cable length with this RFI filter?

The 131N9828 has the H3 filter: RFI class A1/B (C1) with a reduced motor cable length. The exact limit for this frame is in the Danfoss VLT HVAC Drive FC 102 Design Guide (see Technical Documents). If your screened cable run is longer, contact us and we will suggest an alternative.

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

What output current does it deliver at 400 V and at 480 V?

Continuous output current is 8.2 A; intermittent current is 9.02 A. Always size on the motor nameplate current at your supply voltage.

Can this drive be wall mounted without a panel?

Yes. The IP55 / UL Type 12, A4 frame enclosure is designed for direct mounting.

Type code decoded

FC-102P4K0T4Z55H3XGX1OXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
4.0 kW / 5.0 HPP4K0
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP55 / UL Type 12, A4 frameZ55
RFI filter
Position 16–17
RFI class A1/B (C1) with reduced motor cable lengthH3
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
Mains disconnect1
Adaptation A
Position 22
Metric cable entriesO
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX