Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131N3538 VLT HVAC Drive FC 102, rated at 315 kW / 450 HP with 600 A output current for 380-480 V AC three-phase HVAC motor control applications, supplied as an IP00 chassis drive with Commercial C2 RFI filter, DeviceNet MCA 104, no brake chopper, no mains option, no B option and coated PCB.
The Danfoss 131N3538 is a 315 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP00 / chassis unit, built for mounting inside a control panel or enclosure.
This configuration has RFI class A1 (C2), no brake chopper, a graphical LCP 102 control panel, and a DeviceNet MCA 104 fieldbus card. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same 315 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 315 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP00 | |
| EMC Filter | Commercial | |
| Model code | FC-102P315T4E00H4XGCXXXSXXXXA4BXCXXXXDX | |
| Drive series | VLT HVAC Drive FC 102 | |
| Product type | Variable frequency drive / HVAC inverter drive | |
| Power rating | 315 kW / 450 HP | |
| Output current | 600 A | |
| Supply voltage | 380–480 V AC | |
| Input phase | Three-phase | |
| Enclosure rating | IP00 / chassis | |
| RFI filter | Commercial C2 | |
| Brake chopper | No brake chopper | |
| Mains option | No mains option | |
| A option | DeviceNet MCA 104 | |
| B option | No B option | |
| PCB coating | Coated PCB |
This unit is fitted with a DeviceNet MCA 104 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.
Yes. IP00 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.
FC-102P315T4E00H4XGCXXXSXXXXA4BXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 315 kW | P315 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP00 / chassis | E00 |
| RFI filter Position 16–17 | RFI class A1 (C2) | H4 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Conformal-coated PCBs | C |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | DeviceNet MCA 104 | A4 |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |