Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131L4813 VLT HVAC Drive FC-102, an 800 kW three-phase AC variable frequency drive designed for HVAC systems, pumps, fans and industrial motor control applications.
£91,748.80
The Danfoss 131L4813 is an 800 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame F4, IP54 with heater, light and 230 V supply unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A1 (C2), brake chopper + Safe Stop, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Tick the specs you need, then view products that match.
| Power | 800 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP54 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC-102 | |
| Product type | AC variable frequency drive | |
| Rated output power | 800 kW | |
| Motor rating | 1200 HP | |
| Input voltage | 380–480 V AC | |
| Input phases | 3-phase | |
| Protection rating | IP54 | |
| RFI filter | Class A1 (C2) | |
| Brake function | Integrated brake chopper | |
| Safety function | Safe Stop | |
| Frame size | F4 | |
| Dimensions (H × W × D) | approx. 2204 × 2400 × 606 mm | |
| Weight | approx. 1037 kg |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP54 with heater, light and 230 V supply enclosure is designed for direct mounting.
FC-102P800T4R5XH4UGCJXXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 800 kW | P800 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP54 with heater, light and 230 V supply | R5X |
| RFI filter Position 16–17 | RFI class A1 (C2) | H4 |
| Brake / Safe Stop Position 18 | Brake chopper + Safe Stop | U |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Conformal-coated PCBs | C |
| Mains option Position 21 | Circuit breaker + fuses | J |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies