131H9748 Danfoss VLT HVAC Drive 4.0 kW/5.5HP 380-480VAC IP55

131H9748 Danfoss VLT HVAC Drive 4.0 kW/5.5HP 380-480VAC IP55

Danfoss 131H9748 VLT HVAC Drive FC 102: 4 kW / 5.5 HP, 3 × 380–480 V AC supply, IP55 / UL Type 12. Configured with RFI class A2 (C3), no brake chopper, graphical local control panel (LCP 102).

SKU: 131H9748Alt SKU: FC-102P4K0T4E55H2XGXXXXSXXXXAGBXCXXXXDXMPN: 131H9748
Price
List Price £1,432.00 ex VAT
Your Price (ex VAT) Save 45%
£787.60 45% OFF
You save £644.40 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £787.60
Trade pricing is personalised to your account

Manufacturer Lead Time

£787.60

Danfoss 131H9748 at a glance

The Danfoss 131H9748 is a 4 kW / 5.5 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP55 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A2 (C3), no brake chopper, a graphical LCP 102 control panel, and a LonWorks MCA 108 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP55 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Same 4 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 4 kW
Voltage 480 V
Phase Three Phase
IP Rating IP55
Manufacturer Danfoss
Series VLT HVAC Drive FC 102
Type code FC-102P4K0T4E55H2XGXXXXSXXXXAGBXCXXXXDX
Rated output power 4 kW / 5.5 HP
Input voltage 3 × 380–480 V AC
Input phases Three phase
Protection rating IP55 / UL Type 12
RFI filter RFI class A2 (C3)
Brake / Safe Stop No brake chopper
Control panel Graphical local control panel (LCP 102)
PCB coating Standard (uncoated) PCBs
Mains option No mains option
Catalogue number FC-102P3K0T4E55H2XGXXXXSXXXXAGBXCXXXXDX
Product type AC variable frequency drive
Rated output current 6.3 A
Horsepower rating 4.0 HP
Frequency 50 / 60 Hz
Mounting type Wall / panel mounting
Frame size A5
Dimensions (H × W × D) approx. 420 × 242 × 200 mm
Weight approx. 10.79 kg

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a LonWorks MCA 108 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Can this drive be wall mounted without a panel?

Yes. The IP55 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102P4K0T4E55H2XGXXXXSXXXXAGBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
4 kW / 5.5 HPP4K0
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP55 / UL Type 12E55
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
LonWorks MCA 108AG
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX