Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131H8365 VLT HVAC Drive FC-102, a 4.0 kW three phase HVAC variable frequency drive with IP55 Type 12 backplate enclosure, RFI Class A1/B filter, mains disconnect and no local control panel.
£793.10
The Danfoss 131H8365 is a 4.0 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A5, IP55 / UL Type 12 with backplate unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A1/B (C1) with reduced motor cable length, no brake chopper, and no local control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 4 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 4 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP55 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC-102 | |
| SKU / MPN | 131H8365 | |
| Product type | HVAC variable frequency drive / frequency converter | |
| Rated output power | 4.0 kW | |
| Horsepower rating | 5.0 HP | |
| Input voltage | 380-480 V AC | |
| Input phases | 3-phase | |
| Output phases | 3-phase | |
| Protection rating | IP55 / Type 12 backplate | |
| EMC Filter | RFI Class A1/B (C1) | |
| Brake chopper | No brake chopper | |
| Mains option | Mains disconnect | |
| Control panel | No local control panel | |
| PCB coating | Not coated PCB | |
| A option | No A option | |
| B option | No B option | |
| C1 option | No C1 option | |
| D option | No D option | |
| Frame size | A5 | |
| Cable entry | Standard cable entries | |
| Software | Latest release standard software | |
| Dimensions (H × W × D) | approx. 420 × 242 × 200 mm | |
| Weight | approx. 12.2 kg |
The 131H8365 has the H3 filter: RFI class A1/B (C1) with a reduced motor cable length. The exact limit for this frame is in the Danfoss VLT HVAC Drive FC 102 Design Guide (see Technical Documents). If your screened cable run is longer, contact us and we will suggest an alternative.
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP55 / UL Type 12 with backplate enclosure is designed for direct mounting.
FC-102P4K0T4P55H3XXX1XXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 4.0 kW | P4K0 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP55 / UL Type 12 with backplate | P55 |
| RFI filter Position 16–17 | RFI class A1/B (C1) with reduced motor cable length | H3 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | No local control panel | X |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | Mains disconnect | 1 |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.