131H6225 Danfoss VLT FC-102 HVAC Drive 110 kW, 380 - 480 VAC, IP54

131H6225 Danfoss VLT FC-102 HVAC Drive 110 kW, 380 – 480 VAC, IP54

Danfoss 131H6225 VLT HVAC Drive FC 102, rated at 110 kW / 150 HP for 380-480 V AC three-phase HVAC motor control applications, supplied in an IP54 / Type 12 enclosure with Commercial C2 RFI filter, Safe Stop, PROFIBUS DP MCA 101, no mains option, no B option and not coated PCB.

SKU: 131H6225Alt SKU: FC-102P110T4E54H4TGXXXXSXXXXA0BXCXXXXDXMPN: 131H6225
Price on application Contact us for pricing and availability.
Call 01708 343600

Danfoss 131H6225 at a glance

The Danfoss 131H6225 is a 110 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP54 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1 (C2), safe Stop, no brake chopper, a graphical LCP 102 control panel, and a PROFIBUS DP MCA 101 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP54 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1 (C2). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 110 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 110 kW
Voltage 480 V
Phase Three Phase
IP Rating IP54
EMC Filter Commercial
Drive series VLT HVAC Drive FC 102
Product type Variable frequency drive / HVAC inverter drive
Power rating 110 kW / 150 HP
Supply voltage 380–480 V AC
Input phase Three-phase
Enclosure rating IP54 / Type 12
RFI filter Commercial C2
Safety function Safe Stop
A option PROFIBUS DP MCA 101
B option No B option
Mains option No mains option
PCB coating Not coated PCB

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a PROFIBUS DP MCA 101 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Can this drive be wall mounted without a panel?

Yes. The IP54 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102P110T4E54H4TGXXXXSXXXXA0BXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
110 kWP110
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP54 / UL Type 12E54
RFI filter
Position 16–17
RFI class A1 (C2)H4
Brake / Safe Stop
Position 18
Safe Stop, no brake chopperT
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
PROFIBUS DP MCA 101A0
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX